KEY OPTION
58
S/W
Function (Communication Tracking)
K5
ON
Manually setting address of indoor unit (default)
OFF
Automatically setting address of indoor unit
K5: Auto/Manual Address Setting [Applicable Only to RD***M**** Model]
S/W
Function (Snowdrift Protection Control)
K6
ON No use of snowdrift protection control function (default)
OFF Use of snowdrift protection control function
K6: Option for Snowdrift Protection Control [Common to All Models]
When the snowdrift protection control function is set to ON, the outdoor fan operates once for a minute every 30 minutes
when the air conditioner is running under 5 .
K11, K12: Cooling Capacity Option
Use to adjust the cooling capacity. [Common to all models]
The cooling operation raises the frequency when the current pressure is lower than the target pressure, or in the opposite case,
lowers the frequency. When the target pressure is high, the discharge air temperature of the indoor unit increases along with an increase in energy consumption.
It is recommended you keep the factory shipping settings. Please proceed with the adjustment when you wish to lower the energy consumption or
the cooling is not satisfactory.
As the target pressure decreases, the energy consumption and noise are reduced and also, the air discharge temperature of indoor unit decreases.
S/W
Function (Snowdrift Protection Control)
K11 K12
ON ON No adjustment for target pressure (default)
ON OFF 90 %
OFF ON 95 %
OFF OFF 110 %
K7, K8: Setup Value Change Option for Cooling Target Evaporation Temperature [Common to All Models]
Please raise the setting values by improving performance while referring to the performance data of long-pipe cooling from the Technical Data Book.
In the case of short-piping, an unpleasant feeling can be felt from the low discharge air temperature of the indoor unit when the performance is raised arbitrarily.
This is an option for compensating performance in case of long-piping installation.
Please try not to use this function for other purposes.
S/W
Function (Snowdrift Protection Control)
K7 K8
ON ON 7 ~ 9 (factory shipment setting)
ON OFF 5 ~ 7
OFF ON 9 ~ 11
OFF OFF 10 ~ 12
K9, K10: Silent night option. It is possible to run the unit quietly at nighttime by lowering the outdoor FAN RPM
[common to all models]
S/W
Function (Snowdrift Protection Control)
K9 K10
ON ON No use of silent night function (default)
ON OFF STEP - 1
OFF ON STEP - 2
OFF OFF STEP - 3
K15, K16 : Defrost Option when it is desired to change the entry condition of defrosting.
Switch
Function
K15 K16
ON ON MID
OFF ON LOW1
OFF OFF LOW2
The defrost function operates when the temperature difference between outdoor temperature and outdoor heat exchanger temperature is beyond a certain level.
The factory shipping setting is MID. The frost operating temperature gets lowered when changing the option to LOW.
When lowering the temperature of defrosting operation, it has the advantage of lower operation time.
However since it lengthens the operation time after being frozen, the cooling performance is lowered and therefore, the operation time increases.
Use when you wish to adjust the option in the humid area where the defrost function is used quite frequently.
It is recommended you keep the factory shipping settings.
K13, K14: Current Limiting Option Use this function when you wish to adjust the current.
Switch Function
K13 K14 3.5~4.0HP 5.0HP 5.0~7.5HP
ON ON Default Default Default
ON OFF Maximum current - 4(A) Maximum current - 2(A) Maximum current - 2(A)
OFF ON Maximum current - 6(A) Maximum current - 4(A) Maximum current - 4(A)
OFF OFF Maximum current - 8(A) Maximum current - 6(A) Maximum current - 6(A)
S/W
Function (Communication Tracking)
K5
ON
Manually setting address of indoor unit (default)
OFF
Automatically setting address of indoor unit
K5: Auto/Manual Address Setting [Applicable Only to RD***M**** Model]
S/W
Function (Snowdrift Protection Control)
K6
ON No use of snowdrift protection control function (default)
OFF Use of snowdrift protection control function
K6: Option for Snowdrift Protection Control [Common to All Models]
When the snowdrift protection control function is set to ON, the outdoor fan operates once for a minute every 30 minutes
when the air conditioner is running under 5 .
K11, K12: Cooling Capacity Option Use to adjust the cooling capacity. [Common to all models]
The cooling operation raises the frequency when the current pressure is lower than the target pressure, or in the opposite case,
lowers the frequency. When the target pressure is high, the discharge air temperature of the indoor unit increases along with an increase in energy consumption.
It is recommended you keep the factory shipping settings. Please proceed with the adjustment when you wish to lower the energy consumption or
the cooling is not satisfactory.
As the target pressure decreases, the energy consumption and noise are reduced and also, the air discharge temperature of indoor unit decreases.
S/W
Function (Snowdrift Protection Control)
K11 K12
ON ON No adjustment for target pressure (default)
ON OFF 90 %
OFF ON 95 %
OFF OFF 110 %
K7, K8: Setup Value Change Option for Cooling Target Evaporation Temperature [Common to All Models]
Please raise the setting values by improving performance while referring to the performance data of long-pipe cooling from the Technical Data Book.
In the case of short-piping, an unpleasant feeling can be felt from the low discharge air temperature of the indoor unit when the performance is raised arbitrarily.
This is an option for compensating performance in case of long-piping installation.
Please try not to use this function for other purposes.
S/W
Function (Snowdrift Protection Control)
K7 K8
ON ON 7 ~ 9 (factory shipment setting)
ON OFF 5 ~ 7
OFF ON 9 ~ 11
OFF OFF 10 ~ 12
K9, K10: Silent night option. It is possible to run the unit quietly at nighttime by lowering the outdoor FAN RPM
[common to all models]
S/W
Function (Snowdrift Protection Control)
K9 K10
ON ON No use of silent night function (default)
ON OFF STEP - 1
OFF ON STEP - 2
OFF OFF STEP - 3
K15, K16 : Defrost Option when it is desired to change the entry condition of defrosting.
Switch
Function
K15 K16
ON ON MID
OFF ON LOW1
OFF OFF LOW2
The defrost function operates when the temperature difference between outdoor temperature and outdoor heat exchanger temperature is beyond a certain level.
The factory shipping setting is MID. The frost operating temperature gets lowered when changing the option to LOW.
When lowering the temperature of defrosting operation, it has the advantage of lower operation time.
However since it lengthens the operation time after being frozen, the cooling performance is lowered and therefore, the operation time increases.
Use when you wish to adjust the option in the humid area where the defrost function is used quite frequently.
It is recommended you keep the factory shipping settings.
K13, K14: Current Limiting Option Use this function when you wish to adjust the current.
Switch Function
K13 K14 3.5~4.0HP 5.0HP 5.0~7.5HP
ON ON Default Default Default
ON OFF Maximum current - 4(A) Maximum current - 2(A) Maximum current - 2(A)
OFF ON Maximum current - 6(A) Maximum current - 4(A) Maximum current - 4(A)
OFF OFF Maximum current - 8(A) Maximum current - 6(A) Maximum current - 6(A)
스위
기능 (통신 트래킹)
K5
ON 수동으로 실내기 주소 설정(기본값)
OFF 자동으로 실내기 주소
K5 : 수동/자동 [RDM 모델만 해당]
스위
기능 (적설방지 제어)
K6
ON 적설방지 제어 사용 안함(기본값)
OFF 적설방지 제어 사용
K6 : 적설 [전모델 공통]
으로 설정 5 하에 /난방 에서 30 한번1분 실외 FAN .
K11, K12 : 난방 조절 용합. [전모델 공통]
전은 으면 주파 시키, 대의 우에파수를 하강킵니. 내기 토출 아지
니다.
본적으 출하 태를 유지 것을 권장. 나, 에너 소비 키고자 하거 난방 만족 있을 경우 라서 조절 하십시오.
압을 수록 너지 소비 음은 온도 아집니.
스위
K11 K12
ON ON 공장 출하
ON OFF 난방능력 : 90 %
OFF ON 난방능력 : 95 %
OFF OFF 난방능력 : 110 %
K7, K8 : 냉방 온도 변경 [전모델 공통]
양은 Technical Data book의 참조하여 성능 상승.
승시 경우 공기 습니. 설치 성능 션입.
용은 삼가 십시.
스위
기능 (목표 증발온도 설정)
K7 K8
ON ON 7 ~ 9 (공장 출하 세팅)
ON OFF 5 ~ 7
OFF ON 9 ~ 11
OFF OFF 10 ~ 12
K9, K10 : 야간 정음 , 실외 FAN RPM 떨어 야간 조용
[전모델 공통]
스위
기능 (야간 정음)
K9 K10
ON ON 야간 정음 사용 안함 (기본값)
ON OFF STEP - 1
OFF ON STEP - 2
OFF OFF STEP - 3
K15, K16 : Defrost Option 제상 진입 조건변경고자 사용니다.
스위
K15 K16
ON ON MID
OFF ON LOW1
OFF OFF LOW2
전은 온도 정이상 벌어 .
하상태 MID입니다. Option을 LOW 변경 아집니. 도가 운전 있으나,
착상 전되는 시간 므로 길어집니다. 역에서 제상 에서 조정이
필요 .
본적으 장합.
K13, K14 : 제한 전류한을 조절고자 사용니다.
Switch 기능
K13 K14 3.5~4.0HP 5.0HP 5.0~7.5HP
ON ON Default Default Default
ON OFF Maximum current - 4(A) Maximum current - 2(A) Maximum current - 2(A)
OFF ON Maximum current - 6(A) Maximum current - 4(A) Maximum current - 4(A)
OFF OFF Maximum current - 8(A) Maximum current - 6(A) Maximum current - 6(A)
S/W
Function (Communication Tracking)
K5
ON
Manually setting address of indoor unit (default)
OFF
Automatically setting address of indoor unit
K5: Auto/Manual Address Setting [Applicable Only to RD***M**** Model]
S/W
Function (Snowdrift Protection Control)
K6
ON No use of snowdrift protection control function (default)
OFF Use of snowdrift protection control function
K6: Option for Snowdrift Protection Control [Common to All Models]
When the snowdrift protection control function is set to ON, the outdoor fan operates once for a minute every 30 minutes
when the air conditioner is running under 5 .
K11, K12: Cooling Capacity Option Use to adjust the cooling capacity. [Common to all models]
The cooling operation raises the frequency when the current pressure is lower than the target pressure, or in the opposite case,
lowers the frequency. When the target pressure is high, the discharge air temperature of the indoor unit increases along with an increase in energy consumption.
It is recommended you keep the factory shipping settings. Please proceed with the adjustment when you wish to lower the energy consumption or
the cooling is not satisfactory.
As the target pressure decreases, the energy consumption and noise are reduced and also, the air discharge temperature of indoor unit decreases.
S/W
Function (Snowdrift Protection Control)
K11 K12
ON ON No adjustment for target pressure (default)
ON OFF 90 %
OFF ON 95 %
OFF OFF 110 %
K7, K8: Setup Value Change Option for Cooling Target Evaporation Temperature [Common to All Models]
Please raise the setting values by improving performance while referring to the performance data of long-pipe cooling from the Technical Data Book.
In the case of short-piping, an unpleasant feeling can be felt from the low discharge air temperature of the indoor unit when the performance is raised arbitrarily.
This is an option for compensating performance in case of long-piping installation.
Please try not to use this function for other purposes.
S/W
Function (Snowdrift Protection Control)
K7 K8
ON ON 7 ~ 9 (factory shipment setting)
ON OFF 5 ~ 7
OFF ON 9 ~ 11
OFF OFF 10 ~ 12
K9, K10: Silent night option. It is possible to run the unit quietly at nighttime by lowering the outdoor FAN RPM
[common to all models]
S/W
Function (Snowdrift Protection Control)
K9 K10
ON ON No use of silent night function (default)
ON OFF STEP - 1
OFF ON STEP - 2
OFF OFF STEP - 3
K15, K16 : Defrost Option when it is desired to change the entry condition of defrosting.
Switch
Function
K15 K16
ON ON MID
OFF ON LOW1
OFF OFF LOW2
The defrost function operates when the temperature difference between outdoor temperature and outdoor heat exchanger temperature is beyond a certain level.
The factory shipping setting is MID. The frost operating temperature gets lowered when changing the option to LOW.
When lowering the temperature of defrosting operation, it has the advantage of lower operation time.
However since it lengthens the operation time after being frozen, the cooling performance is lowered and therefore, the operation time increases.
Use when you wish to adjust the option in the humid area where the defrost function is used quite frequently.
It is recommended you keep the factory shipping settings.
K13, K14: Current Limiting Option Use this function when you wish to adjust the current.
Switch Function
K13 K14 3.5~4.0HP 5.0HP 5.0~7.5HP
ON ON Default Default Default
ON OFF Maximum current - 4(A) Maximum current - 2(A) Maximum current - 2(A)
OFF ON Maximum current - 6(A) Maximum current - 4(A) Maximum current - 4(A)
OFF OFF Maximum current - 8(A) Maximum current - 6(A) Maximum current - 6(A)
S/W
Function (Snowdrift Protection Control)
K11 K12
ON ON No adjustment for target pressure (default)
ON OFF default - 2.0 kgf/
OFF ON default - 1.0 kgf/
OFF OFF default + 1.0 kgf/
S/W
Function
K15 K16
ON ON MID
OFF ON LOW1
OFF OFF LOW2
S/W Function
K13 K14 4.0HP 5.0HP 5.0HP
ON ON Default
Default Default
ON OFF Maximum current - 4(A)
Maximum current - 2(A) Maximum current - 2(A)
OFF ON Maximum current - 6(A)
Maximum current - 4(A) Maximum current - 4(A)
OFF OFF Maximum current - 8(A)
Maximum current - 6(A) Maximum current - 6(A)
S/W Function
K13 K14 3.5~4.0HP 5.0HP 5.0~7.5HP
ON ON Default
Default Default
ON OFF Maximum current - 2(A)
Maximum current - 1(A) Maximum current - 1(A)
OFF ON Maximum current - 3(A)
Maximum current - 2(A) Maximum current - 2(A)
OFF OFF Maximum current - 4(A)
Maximum current - 3(A) Maximum current - 3(A)
<Single-phase model>
<3phase model>

Related product manuals