EasyManua.ls Logo

Samsung AR Series - Page 41

Samsung AR Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ignition sources free
• Make sure to store the units in a place without
continuously operating ignition sources (for
example, open flames, an operating gas appliance
or an operating electric heater).
• The service engineers shall not use any ignition
sources with the risk of fire or explosion.
• Potential ignition sources shall be kept away from
the work area where the flammable refrigerant can
possibly be released to the surrounding.
• The work area should be checked to ensure that
there are no flammable hazards or ignition risks.
The “No Smoking” sign shall be attached.
• Under no circumstances shall potential sources of
ignition be used while in detection of leakage.
• Make sure that the seals or sealing materials have
not degraded.
• Safe parts are the ones with which the worker can
work in a flammable atmosphere. Other parts may
result in ignition due to leakage.
• Replace components only with parts specified by
Samsung. Other parts may result in the ignition of
refrigerant in the atmosphere from a leak.
Area ventilation
• Make sure that the work area is well ventilated
before performing a hot work.
• Ventilation shall be made even during the work.
• The ventilation should safely disperse any
released gases and preferably expel them into the
atmosphere.
• Ventilation shall be made even during the work.
Leakage detection methods
• The leakage detector shall be calibrated in a
refrigerant-free area.
• Make sure that the detector is not a potential
source of ignition.
• The leakage detector shall be set to the LFL (lower
flammability limit).
• The use of detergents containing chlorine shall be
avoided for cleaning because the chlorine may react
with the refrigerant and corrode the pipings.
• If leakage is suspected, naked flames shall be
removed.
• If a leakage is found while in brazing, the entire
refrigerant shall be recovered from the product or
isolated (e.g. using shut-off valves). It shall not be
directly released to the environment. Oxygen free
nitrogen (OFN) shall be used for purging the system
before and during the brazing process.
• The work area shall be checked with an appropriate
refrigerant detector before and during work.
• Ensure that the leakage detector is appropriate for
use with flammable refrigerants.
Labelling
• The parts shall be labelled to ensure that they have
been decommissioned and emptied of refrigerant.
• The labels shall be dated.
• Make sure that the labels are affixed on the system
to notify it contains flammable refrigerant.
Recovery
• When removing refrigerant from the system for
servicing or decommissioning, it is recommended to
remove the entire refrigerant.
• When transferring refrigerant into cylinders, make
sure that only the refrigerant recovery cylinders
are used.
• All cylinders used for the recovered refrigerant shall
be labelled.
• Cylinders shall be equipped with pressure relief
valves and shut-off valves in a proper order.
• Empty recovery cylinders shall be evacuated and
cooled before recovery.
• The recovery system shall operate normally
according to the specified instructions and shall be
suitable for refrigerant recovery.
• In addition, the calibration scales shall operate
normally.
• Hoses shall be equipped with leak-free disconnect
couplings.
• Before starting the recovery, check for the status of
the recovery system and sealing state. Consult with
the manufacturer if suspected.
• The recovered refrigerant shall be returned to the
supplier in the correct recovery cylinders with the
Waste Transfer Note attached.
• Do not mix refrigerants in the recovery units or
cylinders.
• If compressors or compressor oils are to be
removed, make sure that they have been evacuated
to the acceptable level to ensure that flammable
refrigerant does not remain in the lubricant.
• The evacuation process shall be performed before
sending the compressor to the suppliers.
• Only the electrical heating to the compressor body
is allowed to accelerate the process.
• Oil shall be drained safely from the system.
• For installation with handling the refrigerant
(R-32), use dedicated tools and piping materials.
Because the pressure of the refrigerant, R-32 is
approximately 1.6 times higher than that of R-22,
failure to use the dedicated tools and piping
materials may cause rupture or injury. Furthermore,
it may cause serious accidents such as water
leakage, electric shock, or fire.
• Never install a motor-driven equipment to prevent
ignition.
41

Other manuals for Samsung AR Series

Related product manuals