10. Capacity Correction
Outdoor units
Quantum 2.0 : RNS09YBT+RXS09YBT (AR09TSFYBWKNCV+AR09TSFYBWKXCV),
RNS12YBT+RXS12YBT (AR12TSFYBWKNCV+AR12TSFYBWKXCV)
Max Heat 2.0 : RNS09ABT+RXS09ACT (AR09TSFABWKNCV+AR09TSFACWKXCV),
RNS12ABT+RXS12ACT (AR12TSFABWKNCV+AR12TSFACWKXCV)
Wind-Freeā„¢ 2.0 : RNS09ABT+RXS09ABT (AR09TSFABWKNCV+AR09TSFABWKXCV),
RNS12ABT+RXS12ABT (AR12TSFABWKNCV+AR12TSFABWKXCV)
Cooling
Pipe Length (ft)
16 33 41 49 66
Level Difference (m)
49 - - - 0.92 0.9
33 - 0.95 0.94 0.93 0.91
23 - 0.96 0.95 0.94 0.92
16 0.99 0.97 0.96 0.95 0.93
0 1 0.98 0.97 0.96 0.94
-16 0.99 0.97 0.96 0.95 0.93
-23 - 0.96 0.95 0.94 0.92
-33 - 0.95 0.94 0.93 0.91
-49 - - - 0.92 0.9
Heating
Pipe Length (ft)
16 33 41 49 66
Level Difference (m)
49 - - - 0.92 0.9
33 - 0.95 0.94 0.93 0.91
23 - 0.96 0.95 0.94 0.92
16 0.99 0.97 0.96 0.95 0.93
0 1 0.98 0.97 0.96 0.94
-16 0.99 0.97 0.96 0.95 0.93
-23 - 0.96 0.95 0.94 0.92
-33 - 0.95 0.94 0.93 0.91
-49 - - - 0.92 0.9