10. Installation
Electrical wiring work
Power and communication cable configuration
Main power and the ground cable must be withdrawn through the knock-out hole on the bottom-right or right
side of the cabinet.
Withdraw the communication cable from the designated knock-out hole on the bottom-right side of the front part.
Install the power and communication cable using separate cable protection tube.
Fix a protection tube to the knock-out hole on the outdoor unit by using a CD connector or bushing. Make sure to
use insulating bushing.
Main unit
Sub unit
Sub unit
Ground cable Ground cable
Ground cable
Communication
cable
Power
ground cable
Power cable Power cablePower cable
Communication
cable between
outdoor units
Communication
cable between
outdoor units
Protection
tube
ELCB
MCCB+
ELB
or
ELCB
MCCB+
ELB
or
ELCB
MCCB+
ELB
or