EasyManua.ls Logo

Samsung DVM S VRF - Refrigerant Pipe Temper Grade and Thickness

Samsung DVM S VRF
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. Installation
150
Refrigerant pipe installation
Classification
Model name of
indoor unit
Number
of units
Unit amount of
refrigerant (kg/EA)
Amount of additional
refrigerant (kg)
Total amount of additional
refrigerant (kg)
×
∑(
×
)
Indoor unit (
)
4way cassette
(AM071FN4DEH
)
5 0.45 2.25
4.66
4way cassette
(AM112FN4DEH
)
2 0.57 1.14
Neo forte
(
AM028FNTDEH
)
1 0.27 0.27
MCU 2 0.5 1
- Total amount of refrigerant (+) = 11.965+4.66 = 16.625 (kg)
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter (mm) Minimum thickness (mm) Temper grade
Ø 6.35 0.70
Annealed
Ø 9.52 0.70
Ø 12.70 0.80
Ø 15.88 1.00
Ø 19.05 0.90
Drawn
Ø 22.22 0.90
Ø 25.40 1.00
Ø 28.58 1.10
Ø 31.75 1.10
Ø 34.92 1.21
Ø 38.10 1.35
Ø 41.28 1.43
Ø 44.45 1.60
Ø 50.80 2.00
Ø 53.98 2.10
For pipes larger than Ø 19.05, drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be used. If a
annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and cause
personal injury.
CAUTION

Related product manuals