20
Installing a Universal Comm. Kit
Installing IN/OUT sensor
1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200mm (7.87”) after the header of Indoor unit heat exchanger as shown in
the picture.
3. Insulate the EVA IN and OUT sensor so that it is not affected by airow.
4. Install the ROOM temperature sensor on the RA (Return Air) path of Indoor unit.


Selecting the location of EVA_IN/OUT sensor
200 mm


Header
Distributor
Cool mode
Heat mode

Example of ROOM temperature sensor installation
Location of room temperature sensor
Return air
Outdoor air
 Supply air



or outlet can be measured accurately.
NOTE