Installing a Universal Comm. Kit
Installing IN/OUT sensor
1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200mm (7.87”) after the header of Indoor unit heat exchanger as shown in
the picture.
3. Insulate the EVA IN and OUT sensor so that it is not affected by airow.
4. Install the ROOM temperature sensor on the RA (Return Air) path of Indoor unit.
Selecting the location of EVA_IN/OUT sensor
200 mm
Header
Distributor
Cool mode
Heat mode
Example of ROOM temperature sensor installation
Location of room temperature sensor
Return air
Outdoor air
Supply air
•
•
or outlet can be measured accurately.
NOTE