Reference Information
Samsung Electronics15-3
2-1-1 MH18AP1(P2)
■ Cooling(20m–Piping)
Outdoor Indoor P_high P_low T_dis T_suc P_high P_low T_dis T_suc
21 19.60 8.30 60.23 11.19 18.40 7.33 61.80 9.80
21 27 20.40 9.23 58.90 13.62 19.30 8.50 58.80 12.10
32 21.50 10.26 58.20 15.10 20.30 9.80 57.70 14.20
21 29.10 7.60 85.10 9.20 26.40 7.82 81.60 10.70
35 27 32.20 8.70 84.00 11.60 27.30 8.99 78.40 13.10
32 33.20 9.90 81.70 14.50 28.40 10.13 76.80 15.10
21 33.50 8.60 94.80 9.70 33.20 8.10 93.20 10.40
43 27 35.00 8.90 93.20 12.20 33.70 9.00 91.30 12.30
32 37.20 13.34 92.30 17.60 34.40 10.40 88.20 15.40
135% (ex. 035+035) 100% (ex. 026+026)
24296A(1)_2 11/11/05 5:07 PM Page 12-26