4-6 Samsung Electronics
4-1-2 Ourdoor Unit
DISPLAY
EXPLANATION (The error indicated on the PCB display of outdoor unit)
REMARK
Communiaction error(indoor unable to receive data)
Check electrical connection and setting
Outdoor unit communication error(Abnormal data from indoor unit over 60 packet)
Check electrical connection and setting
Indoor unit room temperature sensor error (Open/Short)
Indoor unit heat exchanger in temperature sensor error (Open/Short)
Indoor unit heat exchanger out temperature sensor error (Open/Short)
Indoor unit sensor error-Evaporator pipe in sensor - Self diagnosis
Indoor unit sensor error-Evaporator pipe out sensor - Self diagnosis
Indoor Unit FAN Error
More than two indoor units cool and heat simultaneously
Indoor Unit EEPROM Error
Indoor Unit EEPROM Option Error
Failure of pipe check operation
Check piping connection and setting
No pipe check operation check
- occasion : try to operation after the installation through auto addressing mode without pipe check operation.
Check setting
The number of Indoor unit mismatched
Check electrical connection and setting
Communication error between the outdoor and indoor unit
Check electrical connection and setting
Outdoor communication error between main PCB and sub PCB
Outside temperature sensor error(Short/Open)
- Error level: over 4.9V(-50°C) under 0.4V(93°C)
Condenser temperature sensor error(Short/Open)
- Error level: over 4.9V(-50°C) under 0.4V(93°C)
Outdoor unit sensor error - Condenser out sensor(Short/Open) - Self diagnosis
Compressor Discharge temperature sensor error
Compressor discharge sensor detached - Self diagnosis
Compressor OLP sensor error (Short/Open)
- Error condition : outdoor temperature under -20°C
- Error level : over 4.95V(-30°C) under 0.5V(151°C)
EvaIn1 Sensor Short/Open
EvaIn2 Sensor Short/Open
EvaIn3 Sensor Short/Open
EvaIn4 Sensor Short/Open
EvaIn5 Sensor Short/Open
EvaOut1 Sensor Short/Open
EvaOut2 Sensor Short/Open
EvaOut3 Sensor Short/Open
EvaOut4 Sensor Short/Open
EvaOut5 Sensor Short/Open