Samsung rb195ab** xaa - Sensors and Fan Operation; Sensors; Ambient Sensor; How to Check Sensor Resistances Accurately

Samsung rb195ab** xaa
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
# tsRB195AB RevB 03/30/2011 3
Temperature/Resistance/Voltage Chart for Samsung Refrigerators Sensors
Temp. (Ω) Volts Temp. (Ω) Volts Temp. (Ω) Volts Temp. (Ω) Volts
-29.2°F 64227 4.326 1.4°F 28021 3.685 32.0°F 13290 2.853 62.6°F 6771 2.019
-27.4°F 61012 4.296 3.2°F 26760 3.64 33.8°F 12749 2.802 64.4°F 6521 1.974
-25.6°F 57977 4.264 5.0°F 25562 3.594 35.6 °F 12233 2.751 66.2°F 6281 1.929
-23.8°F 55112 4.232 6.8°F 24425 3.548 37.4 °F 11741 2.7 68.0°F 6052 1.885
-22.0°F 52406 4.199 8.6°F 23345 3.501 39.2 °F 11271 2.649 69.8°F 5832 1.842
-20.2°F 49848 4.165 10.4°F 22320 3.453 41.0°F 10823 2.599 71.6°F 5621 1.799
-18.4°F 47431 4.129 12.2°F 21345 3.405 42.8°F 10395 2.548 75.2°F 5225 1.716
-16.6°F 45146 4.093 14.0°F 20418 3.356 44.6°F 9986 2.498 77.0°F 5000 1.675
-14.8°F 42984 4.056 15.8°F 19537 3.307 46.4°F 9596 2.449 78.8°F 4861 1.636
-13.0°F 40938 4.018 17.6°F 18698 3.258 48.2°F 9223 2.399 80.6°F 4690 1.596
-11.2°F 39002 3.98 19.4°F 17901 3.208 50.0°F 8867 2.35 86.0°F 4218 1.483
-9.4°F 37169 3.94 21.2°F 17142 3.158 51.8°F 8526 2.301 87.8°F 4072 1.447
-7.6°F 35433 3.899 23.0°F 16419 3.107 53.6°F 8200 2.253 89.6°F 3933 1.412
-5.8°F 33788 3.858 24.8°F 15731 3.057 55.4°F 7888 2.205 91.4°F 3799 1.377
-4.0°F 32230 3.816 26.6°F 15076 3.006 57.2°F 7590 2.158 95.0°F 3547 1.309
-2.2°F 30752 3.773 28.4°F 14452 2.955 59.0°F 7305 2.111 96.8°F 3428 1.277
-0.4°F 29350 3.729
30.2°F 13857 2.904 60.8°F 7032 2.064 100.4°F 3204 1.213
Sensors
Defrost The sensor voltage tells the Main PCB to turn off the
Defrost Heater At 50
o
in Freezer, 63
o
in Fridge
Compartment Temp The sensor controls fan/compressor on/
off to maintain temp
Ice Production harvests when the I/M sensor reads 1.5 de-
grees for 5 minutes, Flex Tray Only.
If the door is opened during that 5 minutes harvest is delayed.
Ambient Sensor
Fan Speeds Below 60 degrees condenser fan is off
Defrost Timing The warmer the room the more often
the defrost
How to Check Sensor Resistances Accurately
Make ice slurry. To do this, fill a cup with ice
(preferably crushed), then add water and a teaspoon
of salt to make a slush. Mix thoroughly and allow to sit
for 2 to 3 minutes. This will give you a 32*F refer-
ence. Now, lower the sensor into the mixture and
leave for about 1 minute, then check the resistance. It
should be very close to 13,300 ohms. Before reinstall-
ing the sensor, be sure to rinse it with fresh water and
dry it.
Ranges of ambient temp. Operation
Above 66
Condenser-Fan is ON as soon as the
compressor is on.
61 ~ 65
Condenser-Fan is ON with 5 minutes
delay from the compressor on.
Below 60
Condenser-Fan is OFF regardless of
the compressor operation
Condenser Fan
Delay function