49
Λ
9-3. Recovery of refrigerant
(1) Close the service valve of liquid side and then press the refrigerant recovery
button on outdoor PCB
✻
1)
.
(2) When the low pressure is getting lower enough, close the service valve to press
the refrigerant recovery button again or press key 3. Pressing the button stops the
compressor.
(3) When total amount of refrigerant in the pipe is more than 15kg, the refrigerant may
not be recovered completely even though the refrigerant recovery (pump down) is
performed. So care must be taken.
(4) The pump down time shall not exceed 5 minutes.
(5) Do not operate until the low-pressure progress to the vacuum state when pump is
down. You should operate while checking pressure after connecting the gauge to
the low-pressure side.
Key 1
Pump down
Key 2
Refrigerant charge
Key 3
Reset
Key 4
Test-operation
✻ 1) MUF-✻✻✻
✻ 1) Refrigerant recovery button
✻ 1) RVMH(C)-✻✻✻
Press times
1
2
3
Key 1
Heating refrigerant charge
Heating test operation
Key 2
Cooling refrigerant charge
Cooling test operation
Pump down
Key 3
Reset
Key 4
View Mode
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 49