SAMWONTECH
1st Edition of TEMI2000_Series IM : Dec. 15. 2008 Page 12 / 58
5.5 RRD Command
RRD Command is used to read data in arbitrary single D-Register.
Request Message Frame
Bytes 1 2 3 1 2 1 4 1
Frame STX Address RRD ,
Count
Number
, D-Reg.- 1 ,
1 4 2 1 1
, D-Reg.- n SUM CR LF
Response Message Frame
Bytes 1 2 3 1 2 1 4 1
Frame STX Address RRD , OK , Data - 1 ,
1 4 2 1 1
, Data - n SUM CR LF
Count Number : 1 ~ 64
Data : Hexa-decimal 16bit string 4 character with no decimal point
Example
To read the D-Register D0001 (TEMP.PV) and D0002 (TEMP.SP)
- Request : [stx]01RRD,02,0001,0002[cr][lf]
- Request (with CheckSum) : [stx]01RRD,02,0001,0002B2[cr][lf]
Response data will be same as below, when 50.0 of D0001 (TEMP.PV) and 30.0 of D0002 (TEMP.SP)
- Response : [stx]01RRD,OK,01F4,012C[cr][lf]
- Response (with CheckSum) : [stx]01RRD,OK,01F4,012C18[cr][lf]