5.7 WRD Command
WRD Command is used to write data in arbitrary single D-Register.
▣ Request Message Frame
Bytes 1 2 3 1 2 1 4 1 4
Frame STX Address WRD ,
Count
Number
, D-Reg.- 1 , Data - 1
1 … 1 4 1 4 2 1 1
, … , D-Reg. - n , Data - n SUM CR LF
▣ Response Message Frame
Bytes 1 2 3 1 2 2 1 1
Frame STX Address WRD , OK SUM CR LF
▪ Count Number : 1 ~ 64
▪ Data : Hexa-decimal 16bit string 4 character with no decimal point
◈ Example
To write 50.0 ℃ into the D0102(TEMP.SP) and 0.5 ℃ into the D0106(TEMP.SLOPE) on FIX mode operation.
- Setting TEMP.SP : 50.0 ℃ → Remove decimal point (500) → Hexadecimalize (0x01F4)
- Setting TEMP.SLOPE : 0.5 ℃ → Remove decimal point (5) → Hexadecimalize (0x0005)
- Request : [stx]01WRD,02,0102,01F4,0106,0005[cr][lf]