1st Edition of TEMI2000_Series IM : Dec. 15. 2008 Page 34 / 58
7.8 PID Group
This setting Group is used for 6 PID subsets for Temperature/Humidity and 3 subsets for Temperature only.
█ PID setting D-Register
D-Reg. Symbol Descriptions
D0701 T.RP1 Temperature Reference Point 1 (T1) to define PID ZONE
D0702 T.RP2
D0703 T.RP3
Temperature Reference Point 2 and 3 (T2, T3) to define
PID ZONE
D0705 H.RP1
D0706 H.RP2
Humidity Reference Point 1 and 2 (T1, T2) to define PID
ZONE
D0708 AT_DISPLAY Setting to display or hide AT KEY
D0709 TEMP.AT_POINT Temperature Point for Auto-Tuning
D0710 HUMI.AT_POINT Humidity Point for Auto-Tuning
D0711 HUMI.CMOD Humidity Control Mode
D0715 1.TEMP_P Temperature Proportional band of PID1
D0716 1.TEMP_I Temperature Integral time of PID1
D0717 1.TEMP_D Temperature Differential time of PID1
D0718 1.TEMP_OH Temperature control Output High limit of PID1
D0719 1.TEMP_OL Temperature control Output Low limit of PID1
.
.
.
.
.
.
.
.
.
D0785 6.HUMI_P Humidity Proportional band of PID6
D0786 6.HUMI_I Humidity Integral time of PID6
D0787 6.HUMI_D Humidity Differential time of PID6
D0788 6.HUMI_OH Humidity control Output High limit of PID6
D0789 6.HUMI_OL Humidity control Output Low limit of PID6