What to do if Sanyo Denki SANUPS E11A UPS has no output power?
- MMary MooreAug 14, 2025
If your Sanyo Denki UPS has no output power, several things could be the cause. First, ensure the input wiring is correctly connected and that the input voltage and frequency are within the rated range. Second, check that the MAIN SW is set to “ON”. Third, verify that the output voltage is set correctly in the User Settings Guide. Lastly, the bypass breaker may be tripped and need to be reset.