Outdoor Unit : CMH3172A
Indoor Unit : KMHS0972 × 4
Power Supply : 230V Single Phase 60Hz
< Heating Capacity >
TH : Total Heating Capacity (BTU/h)
1.
Rating conditions (#)
: Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
RATING CAPACITY: 32,000 BTU/hAIR FLOW RATE: 1,130 CFM
OUTDOOR INDOOR
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
W.B. 60 65 70 75 80
(15.6) (18.3) (21.1) (23.9) (26.7)
0 (-17.8) TH 18,270 18,260 18,230 18,200 18,150
3 (-16.1) TH 18,860 18,850 18,820 18,790 18,740
8 (-13.3) TH 20,260 20,250 20,230 20,200 20,150
13 (-10.6) TH 21,720 21,710 21,680 21,650 21,600
18 (-7.8) TH 23,310 23,300 23,280 23,240 23,190
23 (-5.0) TH 24,970 24,960 24,940 24,910 24,850
28 (-2.2) TH 26,690 26,690 26,660 26,630 26,570
33 (0.6) TH 28,460 28,450 28,430 28,400 28,340
38 (3.3) TH 30,190 30,190 30,170 30,140 30,080
43 (6.1) TH 32,020 32,020 # 32,000 31,960 31,900
48 (8.9) TH 33,850 33,850 33,840 33,800 33,740
53 (11.7) TH 35,680 35,680 35,670 35,630 35,570
58 (14.4) TH 37,420 37,430 37,420 37,380 37,320
63 (17.2) TH 39,190 39,200 39,190 39,160 39,100
65 (18.3) TH 39,870 39,880 39,880 39,850 39,790