1-201
1
Simultaneous(Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-U255SHT x2 / SPW-C606VH8
MODEL No.
Indoor Unit SPW-U255SHT x2
Outdoor Unit SPW-C606VH8
POWER SOURCE
380 - 400 - 415 V, 3 phase, 50 Hz
PERFORMANCE
Cooling Heating
Capacity [min~max]
kW 14.0 [2.7~15.0] 15.0 [2.7~17.0]
BTU / h 48,000 [9,200~51,000] 51,000 [9,200~58,000]
Air circulation (Hi / Me / Lo) m
3
/ h 2,160 / 1,800 / 1,560 (1,080 / 900 / 780 x2)
Moisture removal (High) Liters / h 7.0 (3.5 x2)
External static pressure (High) Pa (mmAg) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415
Available voltage range V 342 - 456 342 - 456
Running amperes* A 10.5 9.93 9.51 8.65 8.17 7.83
Max–Running amperes** A
Power input kW 6.12 6.15 6.18 5.06 5.09 5.12
C.O.P W / W 2.29 2.28 2.27 2.97 2.95 2.93
Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat
Timer ON / OFF 72-hours
Fan speeds Indoor / Outdoor 3 and Automatic control / Variable
Airflow direction (Indoor)
Air filter Long-life filter
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL
Refrigerant control
Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm)
Compressor Rotary (SANYO)
Operation sound
Indoor - Hi / Me / Lo
dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable)
Outdoor - Hi dB-A 52 55
Color
(Approximate value)
Indoor
Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Indoor unit Outdoor unit
Limit of tubing length m (ft.) 50 (164)
Limit of tubing length at shipment m (ft.) 5~30(16~98)
Limit of elevation difference
between the two units
m (ft.)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 15 (49)
Refrigerant tube
outer diameter
Liquid tube mm (in.) 9.52 (3 / 8) 9.52 (3 / 8)
Gas tube mm (in.) 15.88 (5 / 8) 15.88 (5 / 8)
Refrigerant amount at shipment kg R410A - 2.75
DIMENSIONS & WEIGHT
Indoor unit Outdoor unit
Unit dimensions
Height mm (in.) 310 (12-7 / 32) 910 (35-53 / 64)
Width mm (in.) 1000 (39-3 / 8) 940 (37-1 / 64)
Depth mm (in.) 686 (27) 340 (13-25 / 64 )
Package dimensions
Height mm (in.) 325 (12-25 / 32) 1010 (39-49 / 64)
Width mm (in.) 1,275 (50-3 / 16) 1015 (39-61 / 64)
Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
Net weight kg (lb.) 32 (71) 76 (168)
Shipping weight kg (lb.) 37 (82) 85 (187)
Shipping volume m
3
(cu.ft) 0.322 (11.6) 0.431 (15.2)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
SM830160-03ClassicPAC-iA4.ind201201SM830160-03ClassicPAC-iA4.ind201201 2010/02/1610:26:192010/02/1610:26:19