1-1. Unit Specifi cations
Concealed-Duct Type SPW-U125HN x4 / SPW-C486VH
MODEL No.
Indoor Unit SPW-U125HN x4
Outdoor Unit SPW-C486VH
POWER SOURCE
220 - 230 - 240 V, 1 phase, 50/60 Hz
PERFORMANCE
Cooling Heating
Capacity [min~max]
kW 12.5 [2.7~13.4] 14.0 [2.7~16.0]
BTU / h 42,500 [9,200~45,500] 48,000 [9,200~54,500]
Air circulation (Hi / Me / Lo) m
3
/ h 2,400 / 2,040 / 1,680 (600 / 510 / 420 x4)
Moisture removal (High) Liters / h 7.2 (1.8 x4)
External static pressure (High) Pa (mmAg) 49 (5.0): at shipment, 69 (7.0): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes* A 26.9 26.1 25.5 25.2 24.4 23.6
Max–Running amperes** A
Power input kW 5.21 5.23 5.26 4.87 4.89 4.92
C.O.P W / W 2.40 2.39 2.38 2.87 2.86 2.85
Max.Starting amperes A
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat
Timer ON / OFF 72-hours
Fan speeds Indoor / Outdoor 3 and Automatic control / Variable
Airflow direction (Indoor)
Air filter Field supply
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-BH80BG.WL
Refrigerant control
Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm)
Compressor Rotary (SANYO)
Operation sound
Indoor - Hi / Me / Lo
dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable)
Outdoor - Hi dB-A 51 54
Color
(Approximate value)
Indoor
Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Indoor unit Outdoor unit
Limit of tubing length m (ft.) 50 (164)
Limit of tubing length at shipment m (ft.) 5~30(16~98)
Limit of elevation difference
between the two units
m (ft.)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 15 (49)
Refrigerant tube
outer diameter
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8)
Gas tube mm (in.) 12.7 (1 / 2) 15.88 (5 / 8)
Refrigerant amount at shipment kg R410A - 2.75
DIMENSIONS & WEIGHT
Indoor unit Outdoor unit
Unit dimensions
Height mm (in.) 310 (12-7 / 32) 910 (35-53 / 64)
Width mm (in.) 700 (27-18 / 32) 940 (37-1 / 64)
Depth mm (in.) 630 (24-26 / 32) 340 (13-25 / 64)
Package dimensions
Height mm (in.) 358 (14-3 / 32) 1010 (39-49 / 64)
Width mm (in.) 891 (35-3 / 32) 1015 (39-61 / 64)
Depth mm (in.) 783 (30-26 / 32) 409 (16-7 / 64)
Net weight kg (lb.) 24 (53) 71 (156.7)
Shipping weight kg (lb.) 28 (62) 80 (176.4)
Shipping volume m
3
(cu.ft) 0.250 (8.8) 0.419 (14.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB