Electrical Characteristics
Indoor Unit : SPW-DR253GH56 Outdoor Unit : SPW-CR253GHL5
SPW-CR253GL5
● Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz
Rating conditions
A 2.29 / 2.31 0.62 / 0.65 12.1 / 12.3 15.01 / 15.26
kW 480 / 530 0.13 / 0.15 2.55 / 2.7 3.16 / 3.38
Full load conditions
A 2.29 / 2.31 0.62 / 0.65 13.44 / 13.48 16.35 / 16.44
kW 480 / 530 0.13 / 0.15 2.8 / 2.88 3.41 / 3.56
Starting amperes A 3 / 3 1 / 1 67 / 73 71 / 77
● Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz
Rating conditions
A 2.29 / 2.31 0.62 / 0.65 13.7 / 13.5 16.61 / 16.46
kW 480 / 530 0.13 / 0.15 2.86 / 2.96 3.47 / 3.64
Full load conditions
A 2.29 / 2.31 0.62 / 0.65 15.6 / 15.2 18.51 / 18.16
kW 480 / 530 0.13 / 0.15 3.25 / 3.29 3.86 / 3.97
Starting amperes A 3 / 3 1 / 1 67 / 73 71 / 77
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions : Indoor Air Temperature 35°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Heating:
Rating Conditions : Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions : Indoor Air Temperature 24°C DB
Outdoor Air Temperature 21°C DB / 15.5°C WB