Operating and Service Instructions
AT10.1 SERIES
MICROPROCESSOR-CONTROLLED
FLOAT BATTERY CHARGER
SINGLE PHASE INPUT
GROUP II
(30 - 100 Adc OUTPUT)
Address: N56 W16665 Ridgewood Drive
Menomonee Falls, WI 53051
Tel: 800-554-2243
Fax: 262-703-3073
Online: www.SBSBattery.com

Table of Contents

Questions and Answers

  • M
    Michael VazquezJul 31, 2025
    What to do if SBS AT10.1 shows E 02 error?
    • W
      William MendezJul 31, 2025
      If your SBS Battery Charger displays error code E 02, it could be due to the battery being discharged below 6 Volts. Allow the charger to run for 24 hours to recharge the battery. If the battery voltage doesn't increase to the normal rating, seek advice from the battery manufacturer. Also, inspect the wiring at the charger's DC output terminals for shorts and check the DC breaker. If the breaker trips again after resetting, there may be an internal short circuit; inspect the internal wiring, DC filter capacitors, and polarity diode. Restart the charger after service.
  • B
    Brandy RodriguezAug 15, 2025
    Why does my SBS AT10.1 display E 03 error?
    • M
      mary20Aug 15, 2025
      To address a High DC Voltage shutdown on the SBS Battery Charger, restart it by turning the AC breaker off and then on again. Ensure that the High DC Voltage alarm setting is higher than the Equalize voltage setting. If the issue persists, it may indicate an internal component failure. Consult the troubleshooting chart on page 52 in Section 3.4 for 'AT10.1 output voltage too high, or not controllable'.

Summary

Manufacturers Warranty

Five-Year Warranty

Covers defects in material and workmanship for five years.

Important Safety Instructions

General Safety Precautions

Lists essential safety guidelines before operating the AT10.1.

Receiving and Installing the AT10.1 Battery Charger

Installation Methods

Covers moving, mounting (wall, floor, rack), transformer taps, and connections.

Operating the AT10.1 Battery Charger

Starting and Initial Setup

Covers startup sequence, installation checks, and initial power-up.

Parameter Settings and Adjustments

Guides on setting voltages, timers, alarms, current limit, and voltmeter accuracy.

Servicing the AT10.1 Battery Charger

Troubleshooting Procedures

Step-by-step guide, error message interpretation, and using the troubleshooting chart.

Replacing Components

Instructions for replacing PC boards, breakers, surge suppressors, and other parts.

Appendix A: Specifications

Appendix B: Accessories and Options

Appendix E: Communications Module

Appendix F: Forced Load Sharing

Appendix G: CE Compliance

SBS AT10.1 SERIES Specifications

General IconGeneral
Amperage10A
Input Voltage100-240VAC
Output Current10A
Charging Current10A
Voltage12V
Output Voltage12V DC
Protection FeaturesOver Voltage, Short Circuit