Programmable S81-HS system Installation and user manual
Page 1 of 3
S81-F7009-1
Description
Control card for addressable devices using XP95/Discovery Apollo protocol. This card can
control up to a maximum of 127 fire detection devices including : smoke, heat, combined
detectors, alarm buttons, control modules, visual and audible alarm devices.
Technical features
Redundancy: No
Number of devices per loop 127
Loop maximum current 400mA
Supply voltage: 22-29Vdc
Quiescent current: 90mA
Operating temperature: -5 / +50 °C
Storage temperature: -30 / +80 °C
Maximum humidity: 95% (RH) non condensing
Hot swap capability: yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED
Indication
Active
Steady on if an input is under alarmed/activated condition
Disabled
Steady on if an input or an output is disabled
Fault
Flashing in case of Fault condition
Loop Fault
Flashing in case of loop short circuit or open loop
Log on Fault
Flashing in case of difference between the detected devices and the programmed ones.
Service
Flashing in case of in case of smoke detectors with dirty lenses
TX Pol.
It lights up every time data are transmitted from the module to loop devices.
RX Pol.
It lights up every time data from loop devices are received
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single
devices, according to the relevant type:
Parameter
Type
Mode
Operating mode
Sensors
Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-
NC
Sensitivity
Sensors
5 sensitivity levels to be selected
Type of indication
Sensors
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm reset
Sensors
Yes/No
Operating mode
Actuators
Continuous-Normally Energised, Continuous-Normally De-
energised, Intermittent, Pulsing
Timing
Actuators
1 to 15 seconds
(only for pulsing and intermittent modes)
Output type
Actuators
Normal / Sounder
Sounder tone
Actuators
15 selectable tones
Sounder volume
Actuators
7 selectable volume levels
Polling LED
Sensors/Actuators
Enable/Disable LED lighting up during polling
Enable/Disable status export to
Hosts
Sensors/Actuators
No, TCP1, TCP2, RS232
Enable/Disable commands
from Hosts on the channel
Sensors/Actuators
No, TCP1, TCP2, RS232
Question and Answer IconNeed help?

Do you have a question about the Scame S81-HS and is the answer not in the manual?

Scame S81-HS Specifications

General IconGeneral
TypeControl Panel
ModelS81-HS
ManufacturerScame
Current Rating16A
Rated insulation voltage Ui500V
Rated impulse withstand voltage Uimp4 kV
MaterialThermoplastic

Summary

Programmable S81-HS System Overview

Product Description

Control card for addressable devices using XP95/Discovery Apollo protocol, supporting up to 127 devices.

Technical Specifications

Details include redundancy, loop capacity, current, voltage, and environmental operating conditions.

Front Panel Status Indicators

Explanation of the 8 LEDs on the front panel and their corresponding indications.

Device Configuration Parameters

Parameters configurable via ProS81 program for single devices, covering operating modes and settings.

Field Connections and Wiring

Bus Connection Methods

Describes connection to field terminal block using flat or multiconductor cable for S81-E2001-1 and S81-E2001-2 buses.

Standard Connection Diagrams

Illustrates loop wiring with flat cable and multiconductor cable for field connections.

Supported Apollo Addressable Devices

XP95 Device Compatibility

Lists XP95 series devices compatible with the S81-HS system, including detectors and call points.

XPander Device Compatibility

Details XPander series devices supported, such as optical smoke, heat, and multisensor detectors.

Discovery Device Compatibility

Encompasses Discovery series devices like smoke detectors, manual call points, and sounders.