System operation in the event of an alarm
FIRE
Delay
Intervention
Buzzer silenced
Reset Alarm/
System
Actuated
Fault
Disable/Enable
Call Fire Brigade
Site Info
Access Code
Zone
Output
Input
Other Elements
Additional
Information
Menu
On
Off
Set Reset
Other
Commands
1 2 3
4 5 6
7 8 9
0
Alarms Faults Disablements Actuations Other Lists
Schrack Seconet
0000 0000 0000 0000 0000
29.01.2020
INTEGRAL
Operation
Faults
System
Power
Disablements
Test Mode
Fire protection
equipment
Call Service
Actuated
Fault
Silence/
Resound
Disable/Enable
1
2
3
4
5
6
7
8 9
10
11
12
13
14
15
16
17
18
ALARMS 04:30
ALARM ZONE 103/1 0001
0001 0000 0000 0000 0000
Fire alarm
A fire alarm is indicated visually and acoustically: The
FIRE
A
indication flashes, the alarm signal sounds and
the detector zone, detector number and the number of
alarms that have been received are displayed on the op-
erating panel display.
Reset (mute) or disable sirens
Only use this function when the building has been com-
pletely cleared.
Pressing the button Silence/ Resound
Q
resets activ-
ated sirens (mutes them), but these are reactivated to-
gether with the arrival of the next alarm. LED lights up, if
the sirens were reset.
Pressing the button Disable/Enable
R
switches off
the main siren and all other sirens and alarm areas. The
LED next to the button and the
O
LED lights up, if the
alarm systems are disabled. The sirens are not activ-
ated, even not in case of an occurring alarm.
Activate intervention/intervention
mode
(Depends on programming; delay function must be ac-
tivated)
If an alarm is received with the delay layer activated, the
beep acknowledgement time sounds and the LED next
to the button Intervention
C
flashes. Pressing the but-
ton Intervention
C
within the acknowledgement time
activates the intervention/intervention mode. The LED
next to the button lights up and the signal tone changes
from acknowledgement time to intervention/interven-
tion mode. The activation of the main detector output is
delayed by the programmed intervention time.
Pressing and holding the button Intervention
C
within
the intervention time shows the remaining intervention
time on the display.
CAUTION
Confirmed fire alarm
If a fire is actually discovered during in-
tervention period, the fire brigade has to
be notified immediately. The manual call
point can be used for immediate alarm
notification.
Reset alarm
(An authorisation code must be entered for this to be
permitted)
Only use this function if it is ensured that there is no
longer any danger or if you are instructed to do so by the
fire brigade. The cause of the alarm message must be
eliminated.
If it has been proven within the intervention period that
there is no fire, then the alarm can be reset by pressing
the Reset Alarm/System
E
button without the fire
brigade being notified.
If the transmission equipment is actuated (LED
Actuated
F
flashes), the alarm can no longer be reset.
Transmission system actuated
If the LED Actuated
F
flashes, then the location offer-
ing assistance has already been informed of the alarm.
Do not press another button, wait for the support and
assistance staff to arrive. Have the necessary plans
ready.