EasyManua.ls Logo

SCHUSTER SWG A 23 - FLUE GAS EXHAUST PIPE CONNECTION

SCHUSTER SWG A 23
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
1,5 m min.
Ventilation of the rooms
The boiler must be installed in an adequate room in
compliance with the standards in force.
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
(3%) slope towards outlet
B11bs
FOR BOILERS WITH NATURAL DRAUGHT
To connect the ue gas exhaust pipe, local and na-
tional standards must be observed
In the event the boiler is replaced, ALWAYS re-
(1%) slope towards outlet
TOTAL LENGTH (LA + LS)
COAXIAL Ø60/100 DOUBLE Ø80
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[Cps]
A
[Cps]
UP TO
[Cps]
0,5 1 3
1+1 8 + 8
40 (20A+20S)
TOTAL LENGTH (LA + LS)
COAXIALØ60/100 DOUBLE Ø80
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[Cps]
A
[Cps]
UP TO
[Cps]
1 2,5 5 3 16
40(20A+20S)
COAXIALØ80/125 DOUBLE Ø60
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[Cps]
A
[Cps]
UP TO
[Cps]
0.75
2.5
7
NA NA NA
Vertical exhaust and intake terminals directed
outside via coaxial or double pipes.
COAXIAL Ø80/125 DOUBLE Ø60
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[Cps]
A
[Cps]
UP TO
[Cps]
NA NA NA NA NA NA
Distancebetween airinlet
pipeand flue gasexhaust
pipe:min250mm-max500.
Horizontal exhaust and intake terminals directed
outside via coaxial or double pipes.
C12
C32
FOR BOILERS WITH FORCED DRAUGHT
place the ue gas pipe as well.
The boiler is type approved for the exhaust congu-
rations listed below:
1,5 m min.
The combustion air is withdrawn directly from
the room where the boiler is installed.
Said room must be ventilated in compliance with
the standards.
NOTE!
Further details in the section
‘Technical Information’
CAUTION
LT total length is a reference value for the dimen-
sioning of the ducts of A (intake) and S (Exhaust).
Subtracting the values of LT reported, at values
of bends / terminals / extensions you get the
value:
if > 0 = OK - POSSIBLE conguration
if < 0 = NO - WRONG conguration
Cps = Loss coefcient specify
Value referred to curves / terminals / extensions
Ø 60 - Ø 80 wich as to subtracted from LT.

Related product manuals