Date Code 20020426 Overcurrent, Voltage, Synchronism Check, Frequency, and Power Elements 3-11
SEL-351-5, -6, -7 Instruction Manual
Figure 3.9: Levels 5 Through 6 Neutral Ground Instantaneous Overcurrent Elements
See Table 4.1 and accompanying note for a list of the directional features available with each
neutral channel (IN) rating.
Settings Ranges
Setting range for pickup settings 50N1P through 50N6P:
0.250–100.000 A secondary (5 A nominal channel IN current input)
0.050–20.000 A secondary (1 A nominal channel IN current input)
0.005–2.500 A secondary (0.2 A nominal channel IN current input)
0.005–1.500 A secondary (0.05 A nominal channel IN current input)
Setting range for definite-time settings 67N1D through 67N4D:
0.00–16000.00 cycles, in 0.25-cycle steps
Setting range for definite-time setting 67N2SD (used in DCB logic):
0.00–60.00 cycles, in 0.25-cycle steps
Note: If channel IN is rated 0.2 A nominal or 0.05 A nominal, then there is an additional 2-
cycle time delay on all the neutral ground instantaneous (50N1–50N6, 67N1–67N6) and
definite-time (67N1T–67N4T) elements. Any time delay provided by the definite-time
settings (67N1D–67N4D) is in addition
to this 2-cycle time delay.
Accuracy
Pickup: ±0.05 A secondary and ±3% of setting (5 A nominal channel IN current input)
±0.01 A secondary and ±3% of setting (1 A nominal channel IN current input)
±1 mA secondary and ±3% of setting (0.2 A nominal channel IN current input)
±1 mA secondary and ±5% of setting (0.05 A nominal channel IN current input)
Timer: ±0.25 cycles and ±0.1% of setting
Transient Overreach: ±5% of setting
Pickup and Reset Time Curves
See Figure 3.5 and Figure 3.6.