EasyManua.ls Logo

Sel SEL-2241 - Specifications - Emissions; Emissions

Sel SEL-2241
8 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Schweitzer Engineering Laboratories, Inc. SEL-2241 Data Sheet
7
Digital Radio Telephone
RF Immunity:
ENV 50204:1995 Severity Level: 10 V/m
at 900 MHz and 1.89 GHz
Conducted RF Immunity: IEC 60255-22-6:2001
Severity Level: 10 Vrms
IEC 61000-4-6:2008
Severity Level: 10 Vrms
Surge Immunity: IEC 60255-22-5:2008
Severity Level: 1 kV Line to Line,
2 kV Line to Earth
IEC 61000-4-5:2005
Severity Level: 1 kV Line to Line,
2 kV Line to Earth
Fast Transient, Burst
Immunity:
IEC 60255-22-4:2008
Severity Level: Class A: 4 kV, 5 kHz;
2 kV, 5 kHz on communications ports
IEC 61000-4-4:2004 + CRGD:2006
Severity Level: 4 kV, 5 kHz
Power Supply Immunity: IEC 61000-4-11:2004
IEC 61000-4-29:2000
IEC 60255-11:2008
Magnetic Field
Immunity:
IEC 61000-4-8:2009
Severity Level: 1000 A/m for 3 seconds,
100 A/m for 1 minute
IEC 61000-4-10:2001
Severity Level: 100 A/m
Surge Withstand
Capability Immunity:
IEEE C37.90.1:2002,
2.5 kV oscillatory, 4 kV fast transient
IEC 60255-22-1:2007
2.5 kV common-mode
1.0 kV differential-mode
Oscillatory Waves
Immunity:
IEC 61000-4-12:2006
Ring Wave: 2 kV common,
1.0 kV differential
Oscillatory: 2.5 kV common,
1.0 kV differential
Common Mode
Disturbance Immunity:
IEC 61000-4-16:2002
Frequency: 0 Hz to 150 Hz
Severity: Level 4, segment 4: 30 Vrms
open-circuit, 15–150 kHz
Emissions
Radiated and Conducted
Emissions:
IEC 60255-25:2000
FCC 15-107:2014
FCC 15-109:2014
Severity Level: Class A
Canada ICES-001 (A) / NMB-001 (A)

Related product manuals