EasyManua.ls Logo

Sel SEL-387A - Validation Pickup Test Values

Sel SEL-387A
7 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overcurrent Elements Page 5 of 7 20120723
Validation Pickup Test Values
The instructor will use the SEL-AMS (Adaptive Multichannel Source) to inject secondary quantities into
the relay terminals to simulate faults (as indicated in Table 1).
Table 1 Simulated F1 Values for Element Pickup Test
Input
(Fault Applied at F1 Location)
Element Fault
IAW1 51P1P
IAW2 51P2P
IAWn (n = 2 in this example) 50NN21P
The instructor will apply the test values to the relay using the SEL-5401 Test System Software
front-panel
function. Apply a value slightly less than the pickup setting, and slowly increase the current magnitude
until the applicable Relay Word bit asserts.
Step 1
Reset relay targets by pushing the {TARGET RESET} pushbutton located on the relay front panel.
Step 2
Clear the Sequential Events Recorder (SER) entries.
You can perform this task by using either the SER C serial port command or the
ACSELERATOR
QuickSet human-machine interface (HMI).
The instructor will apply the fault current.
Step 3
Use the TARn serial port command (n = the Relay Word bit for the element under test) or the
ACSELERATOR QuickSet HMI to verify the overcurrent element pickup.
Step 4
Verify the following
ACSELERATOR QuickSet HMI user-defined target light-emitting diode (LED)
indicators:
Phase time-overcurrent element 51P1P asserts.
Phase time-overcurrent element 51P2P asserts.
Neutral instantaneous overcurrent element 50NN21P asserts.
Record the element in the “Fault” column of Table 1.

Related product manuals