Presstoentersubmenufrommainmenu
Press+or+tochangeparametervalue
Pressortoscroll
throughsubmenu
Factoryset(RST)
Reset
(Factoryset)
YES/NO
DISPLAY
(For1sec)
DESCRIPTION
RANGE
DEFAULT
VALUE
CONDITION
TimeSetting(TM)
Presstoentersubmenufrommainmenu
Press+or+tochangeparametervalue
Pressortoscroll
throughsubmenu
Triptimedelay
0.0-99.9s
Recoverytime
0.0-99.9s
DISPLAY
(For1sec)
DESCRIPTION
RANGE
DEFAULT
VALUE
CONDITION
Hysteresis(HYS)
Presstoentersubmenufrommainmenu
Press+or+tochangeparametervalue
Pressortoscroll
throughsubmenu
Presstoentersubmenufrommainmenu
Press+or+tochangeparametervalue
Pressortoscroll
throughsubmenu
Password(PW)
Password
ENB/DIS
Enable/Disable
passwordprotection
option
Setpassword
0-999
Willbepromptedonly
whenPasswordoption
isenabled
DISPLAY
(For1sec)
DISPLAY
(For1sec)
DESCRIPTION
DESCRIPTION
RANGE
RANGE
DEFAULT
VALUE
DEFAULT
VALUE
CONDITION
CONDITION
S
t
S
off
t
S
on
t
PowerON
delay
0.5-99.9s
Hysteresis
forcurrent
0.1-99.9A
A
H
Hysteresisfor
Asymmetry.
2 20%
A
S
H
Notpromptedfor1P2
networkselection(not
applicablefor900CPR-1)
NOTE :PWoptionwillbeaskedwhentheuserentertheconfig.menuifPWoptionisenabledintheconfigmenu
andtheuserhastoenterthepasswordwhichhehassetintheS.PW(setpassword)option.
Overcurrent
setting
LOCK
YES/NO,(InthisoptionifYESisselectedbytheuser,thenwhenever
theuserenterstheTripValueSetting,initiallyLOCKoptionwillbe
prompted.TheuserwillhavetosetNOafterwhichhecanaccessthe
tripsettingmenu.IftheuserwantstodisableLOCKoption,hecanset
NOwhenLOCKoptionispromptedafterTR2option.)
0.5A -
10-120%ofCT Primarysetting
1.19kA
Thisoptionwillbe
promptedonlywhen
OCoptionismadeON
inconfig.menu.OC
settingcannotgobelow
theUCsetting.e.g.If
UCis50A,OCsetting
cannotgobelow50A
Presskeyfor3sec.toenterorexit TripValueSettingmenu:
TRIPVALUESETTING
Press+or+tochangeparametervalue
Pressortoscroll
throughmainmenu
Thisoptionwillbe
promptedfirstwhenthe
userentersthetrip
settingmenu.Userhas
tosetNOafterwhichhe
canaccessthetrip
settingmenu.
YES/NO
LOCK
DISPLAY
(For1sec)
DESCRIPTION
RANGE
DEFAULT
VALUE
CONDITION
A
<
Undercurrent
setting
0 999A
0-100%ofCT Primarysetting
Thisoptionwillbe
promptedonlywhen
UCoptionismadeON
inconfig.menu.UC
settingcannotgoabove
theOCsetting.e.g.IfOC
is100A,UCsettingwill
belimitedtill100A only.
S
t
Triptimedelay
0.0-99.9s
A
<
ONLINEKEYS
Individualparameterscanbeviewedwitheverypressofkeys.
TripIndicationonpressofkey:Tripvaluewillbedisplayedtillthekeyispressed.
Presskeyfor3sec.toresetmanually
TRIP INDICATION
RESET
MasterPassword: 753
PARAMETER
Current(Rphase)
Current(Y phase)
Current(Bphase)
PhaseAsymmetry
SYMBOL
L1A
L2A
L3A
As
Note: 1)PhaseAsymmetrynotdisplayedfor1P2networkselection.
2)Onlyonephasecurrentwilllbedisplayedfor1P2 .networkselection
900CPR-3
Doc.name:OP INST 900CPROP440-V01(Page3of3)
(Specificationssubjecttochangeasdevelopmentisacontinuousprocess.)
SelecControlsPvt.Ltd.,India
FactoryAddress:
91-22-28476443/1882
I
EL-27/1,ElectronicZone,TTCIndustrialArea,
MIDC,Mahape,NaviMumbai-400710,INDIA.
Tel.No.:+
FaxNo. :+91-22-28471733I Tollfree :1800227353
Website:www.selec.com Email:sales@selec.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Selec 900CPR-1 and is the answer not in the manual?

Selec 900CPR-1 Specifications

General IconGeneral
BrandSelec
Model900CPR-1
CategoryOther
LanguageEnglish