SETTING MANUAL
15
Program group P1
Program group P1 is used for the thermostat user settings. To
change the selected parameter, hold key for approximately 5
seconds. Parameter starts to flash. Press key ( ) or ( ) to
set the parameter value. To store the setted value, again hold
key for approximately 5 seconds. Group P1 contains the
following parameters; (default setting):
- [P1.1] night temperature (6 °C ÷ 26 °C); (17 °C )
- [P1.2] temperature reduction in ECO mode(0 °C ÷ -9 °C); (-3 °C)
- [P1.3] frost protection temperature (0 °C ÷ 20 °C); (6 °C)
- [P1.4] holiday mode temperature (5 °C ÷ 25 °C); (12 °C)
- [P1.5] ED constant (10 min ÷ 50 min); (20 min)
- [P1.6] display of controlled device (- - - none, 1 - boiler,
2 - pump, 3 - mixing valve); (1)
- [P1.7] temperature sensor calibration (-2 °C ÷ 2 °C); (0 °C)
Service group S1
Service group S1 is used for the thermostat service settings. To
change the selected parameter, hold key for approximately 5
seconds. Parameter starts to flash. Press key ( ) or ( )
to set the parameter value. To store the setted value, again hold
key for approximately 5 seconds. Group S1 contains the
following parameters; (default setting):
- [S1.1] group locking
(- - - unlocked, 1 - locked S1, 2 - locked S1 and P1); (1)
- [S1.2] measured temperature round up
(0.1 °C, 0.2 °C, 0.5 °C, 1.0 °C); (0.5 °C)