EasyManua.ls Logo

Senci SC2000i - Page 9

Senci SC2000i
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
·
Connect the ground lead of the machine to the
ground (Earth) terminal 1 and connect the end to
the ground electrode buried in the ground.
CONNECTION NOTES
·Avoid connecting the generator to commercial
power outlet.
·Avoid connecting the generator in parallel with any
other generator
CONNECTION
Before the generator can be connected to a build-
ing’s electrical system , a licensed electrician must
install an isolation (transfer)switch in the build-
ing’s main fuse box. The switch is the connection
point for generator power and allows selection of
generator or main line power to the building .This
will prevent the generator from charging the main
power line (back feeding)when the main power sup-
ply has failed or has been turned off for line repair.
backfeeding can electrocute or injure line mainte -
nance personnel. Also , generator and building
electrical system damage can occur when normal
operating power returns if unit is used without an
isolation switch.
EXTENSION CORD NOTES
Extension cords should be protected by a tough flexible
rubber sheath (I E C 245) or the equivalent to withstand
mechanical
stress.
6

Other manuals for Senci SC2000i

Related product manuals