INSTALLATION INSTRUCTIONS
senvainc.com 1-866-660-8864 1825 NW 167th Place Beaverton Oregon 97006
TG SERIES
Toxic Gas Sensor
BACnet/Modbus/Analog
PRODUCT IDENTIFICATION
Use installation wires rated for 75C and above.
Only qualied trade installers should install, program,
maintain and test system incorporated therein. Installer is
responsible for compliance of all applicable codes.
Read, understand, and follow instructions thoroughly.
The unit and associated systems require routine test and
maintenance as prescribed in the TG Series User’s Manual
section ‘Periodic Test and Maintenance
Do not install in hazardous or classied locations.
De-energize power supply prior to installation.
Gas sensors should not be used as a substitute for proper
installation, use, or maintenance of gas emitting equipment.
This device is designed to detect conditions that could
result in acute eects of gas exposure. It will not fully safeguard
individuals with specic medical conditions. If in doubt,
consult a medical practitioner.
Conduit is prone to condensation if it passes from one
temperature zone to another, such as from indoors to outdoors
or from one part of a building to another. This condensation
may actually drip into the sensor if mounted below, causing
damage and/or poor readings.
In order to prevent condensation and water egress, seal
both the top and bottom of the conduit with a suitable
expanding foam product (such as Polywater
TM
Zipseal
TM
ZIP-
50KIT1) to prevent warm air from entering cold conduit.
Alternatively, berglass insulation may be inserted in the
conduit between the cold and warm sections using a rigid wire
or other method if both ends cannot be sealed. Sealing is the
preferred method.
Conduit air ow entering sensor may prevent sensor from
reading ambient air properly, resulting in under measurement
of gases. Plug sensor conduit in all installations with a foam
plug or seal as noted above in order to prevent airow from
the conduit.
DANGER
WARNING
!
LIMITATION OF LIABILITY
Senvas liability, whether in contract, in tort, under any
warranty, in negligence or otherwise shall not exceed the
amount of the purchase price paid by the purchaser for the
product. Under no circumstances shall Senva be liable for
special or consequential damages.
TG -
Gas1
Pkg
Gas2
Out
Package
R = Recessed Mount
Output Type
A = Analog
B = BACnet/Modbus
Gas Type 1*
C = Carbon Monoxide (CO)
N = Nitrogen Dioxide (NO)
D = Carbon Dioxide (CO2)
E = Dual Channel CO2
M = Methane (CH4)
P = Propane (C3H8)
H = Hydrogen (H2)
O = Oxygen (O2)
S = Hydrogen Sulphide (H2S)
A = Ammonia (NH3)
2 = R22
3 = R134A (Multi-Refrigerant)
4 = R410A
5 = R404A
6 = R407C
Gas Type 2*
X = No second gas
N = Nitrogen Dioxide (NO)
D = Carbon Dioxide (CO2)
E = Dual Channel CO2
M = Methane (CH4)
P = Propane (C3H8)
H = Hydrogen (H2)
O = Oxygen (O2)
S = Hydrogen Sulphide (H2S)
A = Ammonia (NH3)
2-6 = Refrigerants (see above)
*Refrigerant sensors may not be paired with CH4, C3H8, or H2