ERA IS
ELECTRIC/TECHNICAL DIVISION
INSTALLATION INSTRUCTIONS
DESCRIPTION: CL/19 is a level control for conductive liquids, modular enclosure (35 mm) for 46277 DIN rail.
Selection of detection sensitivity (HIGH - LOW) and functions (FILLING o DRAINING ) via microswitches.
The low alternate current applied on the sensors guarantees safety of the CL/19 and eliminates the
undesired effects of electrolysis.
SR 15.19 230V~
SR 15.49 110V~
SR 15.59 24V~
WARNING: CL/19 does not work with: DISTILLED WATER, OILS, HYDROCARBONS,
LOW CONDUCTIVITY LIQUIDS.
WIRING DIAGRAM
Microswitch 2
for selection
High sensitivity (ON)
Low sensitivity (OFF)
Microswitch 1
for selection
g (ON)
Filling (OFF)
Drainin
Relay status indicator
= energised on filling
or draining
On
Off= de-energised CL/19 on standby
GREEN LED
The following SERAI sensors can be
connected to the CL/19: R/1, R/2, R/4,
R/5, R/40, R/3A, R/3B and R/6.
If the tank is in conductive
material, terminal C (common) can be
connected directly to the tank.
WARNING:
SR 15.19 230 ÷ 240V ±10% 50/60Hz~
SR 15.49 110 ÷ 125 V ±10% 50/60Hz~
SR 15.59 24 V ±10% 50/60Hz~
Flashing= sensors in short circuit
Off= mains power off
On= mains power present
Mains power indicator led
SINCE 1965
The CL/19 is equipped with a top quality relay suitable
for virtually all applications. However, the use of
contactors is recommended to control motors with an
output higher than the specified values.
1
2
CL/19
ON
2
SELEZIONE SENSIBILITÀ
SENSITIVITY ADJUSTMENT
2
ON
ON
BASSA
ALTA
LOW
HI
CONTROLLO LIVELLO IN
LEVEL CONTROL
1
ON
1
ON
RIEMPIMENTO
FILLING
SVUOTAMENTO
EMPTYING
RED LED
Motors and pumps: 8A@230V~
max ½ HP
35 X 90 X 70.5mm / 144 g.
IP 20 for terminals
Power supply:
12mA - 230V~
Consumption on standby: ........................
1 changeover
Relay output: ............................................
Resistive: 10A @230V~
Applicable load: ........................................
9V~
Voltage on sensors: .................................
0,9mA Max
Current absorption of immersed sensors:
3 seconds
Activation threshold: ................................
-10 ÷ +60°C
Operating temperature: ...........................
Protection rating: .....................................
Insulation class: .......................................
Dimensions and weight: ..........................
If correctly installed, the device has no accessible parts.
SR 15.69 400V~
SR 15.69 400 ÷ 415V ±10% 50/60Hz~
m
C
A1
A2
M
NC
NO
11
12
14
F
N
SR 15.19 230V~
SR 15.49 110V~
SR 15.59 24 V~
SR 15.69 400V~
C
m
M
E3
E2
E1
Maximum
cable length
250 m.
Section 1mm²
F/R
N/S
*
*
*
(R)
()
(S)
-20 ÷ +70°C
Storage temperature: ...............................
95% condensate-free
Max. relative humidity: .............................
LEVEL CHECK OF CONDUCTIVE LIQUIDS
FOR FILLING OR DRAINING
CL/19
IP 40 for front panel
SINCE 1965
WARNING: If the
controlled liquid shows,
at the operating
temperature, fumes or
condensation, it is
recommended not to
use sensors with the
terminals close to each
other such as sensors
R/1 and R/2.
The condensing
humidity can cause a
bad working of the
level control.
If that is the case, it is
suggested to install
single sensors spaced,
see R/3A, R/4, R/5, R/6,
R/40 etc.
Question and Answer IconNeed help?

Do you have a question about the Serai CL/19 and is the answer not in the manual?

Serai CL/19 Specifications

General IconGeneral
BrandSerai
ModelCL/19
CategoryController
LanguageEnglish

Summary

CL/19 Level Control Installation Guide

Product Description and Limitations

Details the CL/19 level control for conductive liquids and lists incompatible liquid types.

Technical Specifications

Lists electrical parameters, operating conditions, dimensions, and protection ratings.

Wiring Diagram and Component Identification

Illustrates connections, microswitches, LEDs, and terminal labels for installation.

CL/19 Operation and System Configuration

Operating Modes and Sensitivity Settings

Explains filling, draining functions via microswitch 1 and sensitivity via microswitch 2.

Connection Examples

Provides wiring examples for filling and draining configurations with a 3-phase pump.

Installation Safety Warnings

Crucial warnings regarding qualified personnel, residual current circuit breakers, and power disconnection.

Regulatory Compliance and Product Information

Product Category and Directives

Outlines product category, relevant European directives (BT, EMC, RoHS), and standards.

Environmental Disposal and Guarantee

Information on WEEE directive for disposal and 24-month guarantee conditions.