S
The series DGN 75AC offers a whole range of high accuracy program-
mable panel meters. Each instrument is equipped on its front face with a
five 14mm high red digits display, whose brightness suits applications in
industrial control rooms perfectly.
They allow display, control and transmission of data from alternating vol-
tage, alternating current and of frequencies from alternating signals.
•
DGN 75AC
Measurement of an alternating voltage, an alternating current and of the
frequency of an alternating signal.
• 2 programmable voltage calibers : 150V and 500V
Un = 150 VAC and 500 VAC
Overstepping 1.2 Un
• 2 programmable current calibers : 1A and 5A
In = 1.2A and 6A
Overstepping 1.2 In
Automatic caliber on 0-500V, 0-5A possible
• Voltage overload
permanent : 750 V
during 10s : 1000 V
• Current overload
permanent : 10A
during 10s : 50A
• Frequency : 45 Hz to 65 Hz
• Accuracy rating :
0.2 % voltage / current (at 25°C)
• Measure cycle
55 ms
• Display :
3 magnitudes can be programmed for a display accessible simply by
pressing 1 key.
11.. PPRREESSEENNTTAATTIIOONN
AAVVAAIILLAABBLLEE OOPPTTIIOONNSS
: (specify on order)
Insulated analog output
: A
Active or passive current, or voltage output.
Programmable scale ratio with enlarging effect.
Relay output
: R or R4
2 or 4 relays :
Setpoint relays :
mode setpoint or mode window.
Latching function.
Time delay and hysteresis adjustable on each setpoint.
Alarm messages
Insulated digital output : N
RS 485 2 wire, protocole MODBUS-JBUS.
LOGIC input 2 insulated LOGIC inputs with programmable functions
Display hold,
Min. and max. zero reset
Bargraph
: (16 led display) : B
Allows a quick evaluation of the measured value
variations.
Programmable scale factor
Possibility to programme 3 bargraphs (1 for each
displayed parameter)