AY/AE-A079E
AY/AE-A099E
20
The room is not heated at all or not heated.
The compressor does not operate.
The control circuit board is normal.
Refrigerant may be leaked.
The running capacitor may be defective.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The thermistor may be defective.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
NO
Replace the PWB ass'y with a new one.
Push the button of "TEST RUN" on the 
indoor unit, and wait 3 minutes.
Using a tester, measure voltages at the 
terminals on the terminal board.
Select HEAT MODE with remote controller.
And then start operation.
Is the voltage
between terminal "N" and
"2" of the terminal board the
power supply voltage ?
Is the voltage
between terminal "N" and
"3" of the terminal board the
power supply voltage ?
YES
YES
YES
NO
NO
NO