Sharp AU-A129E - Compressor and Thermistor Troubleshooting; Room Not Cooled Diagnosis

Sharp AU-A129E
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AH-A129E
AU-A129E
22
The room is not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may have leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
Push the button "TEST" on the 
indoor unit, and wait 3 minutes.
Is there a voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
correct Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
0
20
40
60
80
100
120
140
160
180
0 10 20 30 40˚C-10
CHARACTERISTIC OF TH1 & TH2
Fig. 1
Using a meter, measure voltage at
the terminals on the terminal board.
K
10˚C
30K