29
AY-XP08/10/13CE
AE-X08/10BE-C
AE-X13BE
BREAK DOWN DIAGNOSIS PROCEDURE
Self-diagnostic procedure using display mode
If the timer lamp blinks during operation, the problem can be diagnosed using the following table.
: Blinks at 2-second intervals : OFF : ON : Blinks 3 times at 0.2-second intervals
Indoor and outdoor unit 
completely stopped
Display by indoor unit operation lamp
Displayed in a pattern which comes on at  the same 
time as the timer lamp
4 seconds off
What to check, procedure
Display by 
outdoor 
unit lamp 
LED 1
Diagnosis
Solution
Condition 
of indoor 
and 
outdoor 
unit
Normal
Once
Twice
3 times
4 times
5 times
6 times
7 times
Compressor lock error
DC overcurrent error
AC overcurrent error
Normal
Does compressor active ? Does it go off immediately after active ?
1. Check the circuit in the power transistor module.
2. Is the outdoor fan revolving ?
1. Is the discharge outlet of the outdoor unit clogged ?
1. Measure the resistance of thermistor TH2 on the outdoor unit
    (see Figure 2).
1. Replace power transistor 
module
1. Clear the discharge outlet.
11 times Power factor module error
In cases when power supply voltage waveshape distortion is large, 
it can be improved by increasing the capacitance of capacitor C8.
C8 :         RC-AZA046JBE0 (1500µF 420V)
Capacitor clamp :         LBNDKA099JBWZ (Same for AE-X13BE)
1. Check wiring of power factor module.
1. Replace the power factor module.
2. Replace C8. (   )
Overheat of the comp-
ressor error
(protector operating) or 
outdoor compressor  
thermistor TH1 short
1. Replace the outdoor control board 
assembly 
(Current transformer wire break.) 
1. Reattach.
2. Replace the outdoor thermistor 
assembly.
1. Replace the outdoor thermistor 
assembly.
1. Clear the discharge outlet.
2. Assure power supply voltage.
3. Refill to rated amount.
4. Replace the outdoor ther-mistor 
assembly.
5. Replace the indoor control board 
assembly or only TH2.
1. Apply an external shock to the 
compressor.
2. Replace the compressor.
1. Can voltage be detected at the current transformer on the outdoor 
unit control board?
1. Are the connectors of the outdoor unit thermistors well attached ?
2. Measure the resistance of thermistors TH1 and TH2 on the 
outdoor unit (see Figure 2).
1. Is the discharge outlet of the outdoor unit clogged ?
2. Is the power supply voltage at least 198 V at full power operation ?
3. Check for refrigerant leaks at the tubing connections.
4. Measure the resistance of compressor thermistor TH1 on the 
outdoor unit (see Figure 2).
5. Measure the resistance of heat exchanger pipe thermistor TH2 on 
the indoor unit (see Figure 1).
AC abnormal current  
error
Open circuit of the 
thermistor error
Short circuit of the  
thermistor error