No. Code
0: No operation.
1: Self-study of rotate parameter: nameplate parameter of the motor (P03.01
~
P03.05) must be input correctly before self-study of motor parameter; and separate the
motor with the load and make the motor have a static and unloaded state, or the result
for self-study of motor parameter may be wrong.
Before self-study of motor parameter, acceleration and deceleration time (P01.11,
P01.12) should be set properly according to the inertia of the motor; or during the self-
study period of motor parameter will have over current and overvoltage fault.
Set P03.11 as 1 and the press to start the self-study of motor parameter;
now LED shows -TUN- and flicks. Press to start the self-study of parameter;
now it shows TUNE0 and TUNE1 ; and then the motor begins to operation; and
RUN/TUNE flicks. After the self-study of parameter, it shows -END- and then it shows
returning to the interface of halt state. When -TUN- flicks , press to exit the state
of self-study.
During the self-study period, can be pressed to terminate the operation for
self-study of parameter.
Notice: the start and stop for self-study of parameter can be only controlled by the
keyboard; after the self-study of parameter, this function will automatically reset to 0.
Static self-study of parameter: during the period for the static self-study of
parameter, it is unnecessary to separate the motor with the load ;
And make the motor have a static and unloaded state, or the result for self-study of
motor parameter may be wrong. Before self-study of motor parameter, nameplate
parameter (P03.01~P03.05) of the motor must be input correctly; rotator resistance of
the motor can be detected after the self-study. However, the mutual inductance and no-
load current can’t be detected and the user can input corresponding value depending on
their experience.
No. Code