What to do if the current output does not change from approximately 3.6mA on my Shinkawa Transmitter?
- CcolemanaliciaAug 4, 2025
If the current output of your Shinkawa Transmitter remains constant at approximately 3.6mA, there might be several reasons: * The sensor may be too close to the target; in this case, you should adjust the sensor. * There might be a short or open circuit in the sensor or extension cable; consider replacing the faulty component. * A foreign substance might be present in a connector; remove it. * The transmitter itself could be faulty, requiring replacement.