(1) Compressor frequency control
According to difference room temperature and set temperature(δt = RT-ST), running
frequency of compressor is controlled by electronic controller. When room temperature is much
higher than set temperature, compressor will start at a high frequency, and as room temperature
goes down, compressor running frequency will go down. When room temperature is lower than set
temperature, compressor will run at very low frequency. In general, unit will change its running
frequency according toδt to make room temperature closing to set temperature.
(2) Outdoor temperature affects running frequency of compressor
Outdoor temperature affect compressor’s running frequency. Difference inlet temperature of
outdoor unit is adapted by diff
erence compressor running frequency. While outdoor temperature is
about 30, the compressor will run in high frequency.
If unit run in “cooling” mode and ou
tdoor temperature is less than -1℃,controller will shut down
compressor and show error code, while the ambient temperature is over 0℃, the compressor will
run automatically.
(3) Auto fan control in cooling mode
In cooling mode (include cooling in “I feel” mode), fan speed is determined by δt, as
the
following diagram:
1.5
1.0
3.0
3.5
δt come down
high fan
δt come up
midium fan
low fan
RT-ST
4. “DRY” Mode Operation
(1) The system for DRY operation used the same refrigerant circle as the cooling one.
(2) When the system operates in DRY mode, at first it operates in cooling mode at 16 or
18 for 3 minutes. After that, the system will operate in cooling mode with lowest fan
speed, meanwhile the set temperature (ST) is “RT-2 which means that the ST is room
temperature at then minus 2. During the course of this mode, the fan speed set operation
and room temperature set are restricted, except the vane motor adjusting.
5. “HEATING” Mode Operation (available for Heat Pump only)
(1) Frequency control
The same as
the frequency control in cooing mode, running frequency of
compressor is
controlled by controller. Unit change its running frequency according to δt to make room
temperature closing to the set temperature.
(2) Indoor fan motor control
1. Cold Air
Prevention C
ontrol
z The function is intended to prevent cold air from being discharged when the heating
operation starts or when defrosting.
z The indoor fan speed will be controlled as following.
5
Air Conditioner Service Manual