1
structure
which
provides
mounting
for
the
power
fuses
,
con
-
trol
transformer
and
primary
fuses
,
and
drawout
attachments
.
Due
to
the
fact
that
arc
interruption
is
accomplished
com
-
pletely
within
the
vacuum
bottles
,
items
such
as
arc
chutes
,
blowout
coils
and
pole
plates
are
not
required
with
vacuum
contactors
.
Stationary
and
movable
power
contacts
are
lo
-
cated
inside
the
vacuum
bottles
with
corrugated
stainless
steel
bellows
attached
to
the
movable
contacts
to
ensure
a
complete
seal
and
integrity
of
the
vacuum
bottle
.
Voltage
surge
suppressors
are
sometimes
furnished
at
the
controller
load
terminals
to
limit
transient
overvoltages
caused
by
multiple
reignitions
which
may
occur
due
to
the
use
of
vacuum
interrupters
.
For
application
guidelines
see
the
instruction
manual
for
Series
81000
Controllers
—
MVC
-
9018
.
General
Siemens
Type
90
H
3
vacuum
contactors
are
provided
for
use
in
Series
81000
medium
voltage
controllers
.
Type
90
H
3
contactors
provide
the
advantage
of
long
mechanical
and
electrical
life
with
low
maintenance
and
are
essentially
im
-
mune
to
adverse
atmospheric
environments
.
They
are
suitable
for
loads
of
all
types
,
including
three
-
phase
motors
,
transformers
,
capacitors
and
resistive
loads
.
The
overall
dimensions
of
the
vacuum
contactor
are
18
inches
(
457
mm
)
wide
by
27.5
inches
(
699
mm
)
high
by
23.87
inches
(
606
mm
)
deep
.
The
vacuum
contactor
with
single
or
double
barrel
power
fuses
can
be
installed
in
Series
81000
Class
E
2
controllers
of
either
one
-
,
two
-
or
three
-
high
construction
.
The
Type
90
H
3
vacuum
contactor
consists
of
:
(
1
)
a
low
voltage
section
which
contains
the
main
coil
drive
and
auxiliary
contacts
;
(
2
)
a
medium
voltage
section
which
houses
the
vacuum
interrupter
bottles
and
(
3
)
a
support
Contactor
Ratings
Interrupting
Capacity
kV
Enclosed
Continuous
Ampere
Rating
Maximum
Voltage
Rating
Impulse
Level
(
BIL
)
Contactor
Type
Fused
Class
E
2
Controller
(
MVA
)
Unfused
Contactor
(
kA
)
5
kV
@
2.3
-
4.6
kV
200
@
2.3
kV
350
@
4.0
kV
400
@
4.6
kV
60
90
H
35
5.0
kV
360
5
kA
@
6.6
kV
60
5
kA
@
6.6
kV
7.2
kV
90
H
37
310
Auxiliary
Contacts
:
Each
contactor
is
equipped
with
3
N
.
O
.
and
4
N
.
C
.
auxiliary
contacts
for
customer
use
.
These
contacts
are
rated
600
V
,
10
A
(
NEMA
Class
A
600
)
.
NOTE
:
On
drawout
contactors
,
2
N
.
O
.
and
2
N
.
C
.
contacts
are
available
for
customer
use
.
Transformer
Loads
3
Phase
Horsepower
Rating
at
Utilization
Voltage
Maximum
Motor
Fuse
Rating
2300
V
4000
-
4600
V
6600
V
Maximum
Transf
Fuse
Rating
Contactor
Type
Maximum
3
-
Phase
kVA
at
Distribution
Voltage
Syn
.
Motors
Syn
.
Motors
Syn
.
Motors
Ind
.
Ind
.
Ind
.
Motors
Motors
Motors
2400
V
4800
V
6900
V
4160
V
0.8
PF
1.0
PF
0.8
PF
1.0
PF
0.8
PF
1.0
PF
450
E
1500
2500
2500
90
H
35
24
R
1750
1500
2500
3000
2500
1500
200
E
18
R
1500
3500
4500
3500
90
H
37
Courtesy of NationalSwitchgear.com