Design (continued)
QRA2 / QRA2M, QRA10 / QRA10M
Ionization probe (must be supplied by customer)
Using an ionization Flame supervision by making use of the electrical conductivity of the flame in
probe conjunction with the rectifying effect is only possible with gas and blue-flame burners.
Since the flame signal amplifier responds only to the DC component of the flame signal
(ionization current), a short circuit between the flame detector and functional earth
cannot simulate a flame signal.
Single-electrode operation, i.e., ignition and supervision with a single electrode, is not
possible. Do not activate the test mode switchover using terminal 6 during flame
supervision with ionization probes. Terminal 6 must be connected directly to the phase
conductor at terminal 1 in this case.
Using an ionization
probe and a UV
flame detector QRA
It is possible to connect an ionization probe and a UV flame detector QRA to the
LFS1.2... at the same time. The flame assessment behaves as follows:
10/40