EasyManua.ls Logo

Siemens POL903.00/100 - Technical Specifications and Disposal; Disposal Guidelines; Technical Data Summary

Siemens POL903.00/100
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6/11
Smart Infrastructure CC1N7219en
10/28/2020
Disposal notes
The WLAN stick contains electrical and electronic components and must not be
disposed of together with domestic waste.
Local and currently valid legislation must be complied with.
Type summary
Article no. Type
S55803-Y130-A100 POL903.00/100
Technical data
Supply voltage (rated voltage) 5 V DC ±10%
Current consumption Typically 120 mA
Max. 200 mA
Degree of protection IP30
Safety class III
Degree of pollution 3
WLAN modes IEEE802.11g and b
Mounting position Optional
Dimensions (L x W x H) 67.5 mm x 22 mm x 10 mm
Cable length between POL903.00/100
WLAN stick and controller
Max. 2.5 m
Weight 10 g
Storage DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -40°C to +60°C
Humidity <90% r.h. (non-condensing)
Transport DIN EN 60068-2 and EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -40°C to +80°C
Humidity 5% to 90% r.h. (non-condensing)
Operation DIN EN 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M2
Temperature range -15°C to +60°C
Humidity <90% r.h. (non-condensing)
Installation altitude Max. 2,000 m above sea level
Please note!
Condensation, formation of ice, and ingress of water are not permitted.
LED signaling
Color code Status / Parameter
Green Initialization
Green, flashing slowly Normal operating status
Green, flashing quickly Communication
Red, flashing While saving a new configuration or during a firmware
upgrade
Red Fault status
General unit data
Environmental
conditions

Related product manuals