Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
211
3.16 Automatic restart
Parameter range: P1210
P1211
Warnings A0571
Faults F0035
Function chart number: -
After a power failure (F0003 "Undervoltage"), the "Automatic restart" function
(enabled using P1210) automatically powers-up the drive inverter again. Any faults
are automatically acknowledged by the drive inverter.
When it comes to power failures (line supply failure), then a differentiation is made
between the following conditions:
Line undervoltage (brownout)
"Line undervoltage" is a situation where the line supply is interrupted and returns
before (if installed) the BOP display has gone dark (this is an extremely short line
supply interruption where the DC link hasn't completely collapsed).
Line failure (blackout)
"Line failure" is a situation where the display has gone dark (this represents a
longer line supply interruption where the DC link has completely collapsed) before
the line supply returns.
The automatic restart function P1210 is shown in the following diagram (refer to
Fig. 3-81) as a function of external states / events.
0
−−−−
1
−−
2
+
−−−
3
++++
4
++
−−
5
+
++
6
++++ +
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
Fault acknowl.
Fault acknowl.
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
ON always active (permanent)
P1210
ON in no-voltage condition
Fault F0003 on All other faults on
BrownoutBlackout BrownoutBlackout
All faults on
Blackout
Restart
No faults on
Blackout
+
Fault acknowl.
restart
Fault acknowl.
Restart
Restart
Fig. 3-81 Automatic restarts

Table of Contents

Other manuals for Siemens Powerblock

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Powerblock and is the answer not in the manual?

Siemens Powerblock Specifications

General IconGeneral
BrandSiemens
ModelPowerblock
CategoryInverter Drive
LanguageEnglish

Related product manuals