Settings
Settings on the “Enduser” level
Press
or to activate the “Enduser” level.
Line
Function, display Factory setting
(Range)
Setting Explanations, notes and tips
1 Setpoint for
NORMAL heating
20.0 °C
(0…35)
…...............°C
2 Setpoint for
REDUCED heating
14.0 °C
(0…35)
…...............°C
3 Setpoint for holiday
mode / frost protec-
tion
10.0 °C
(0…35)
…...............°C
4 Weekday (for heat-
ing program)
1-7
(1…7)
…......................
1 = Monday
2 = Tuesday, etc.
1-7 = entire week
5 First heating period,
start of NORMAL
heating
06:00
(00:00…24:00)
…......................
6 First heating period,
end of NORMAL
heating
22:00
(00:00…24:00)
…......................
7 Second heating
period, start of
NORMAL heating
--:--
(00:00…24:00)
…......................
8 Second heating
period, end of
NORMAL heating
--:--
(00:00…24:00)
…......................
9 Third heating pe-
riod, start of
NORMAL heating
--:--
(00:00…24:00)
…......................
10 Third heating pe-
riod, end of
NORMAL heating
--:--
(00:00…24:00)
…......................
Switching program for heating
circuit
--:-- = period inactive