Block “Basic settings for d.h.w.”
121 Assignment of
d.h.w. heating
0
(0…2)
.........................
D.h.w. heating for
0 = own controller
1 = all controllers in the inter-
connected system that have
the same segment number
2 = all controllers in the inter-
connected system
122 Program for d.h.w.
circulating pump
2
(0…3)
.........................
0 = 24 h per day
1 = according to the heating
program(s), depending on
the setting made on line 121
2 = according to switching
program 2
3 = according to switching
program 3
Block “Release of d.h.w. heating”
123 Release of d.h.w.
heating
2
(0…2)
.........................
0 = released 24 hours a day
1 = released according to the
heating program(s), de-
pending on the setting
made on operating line 121;
start of enabling is shifted
forward by one hour
2 = released according to
switching program 2