Block “Priority and flow temperature setpoint d.h.w.”
D.h.w.
priority
Flow
temperature
setpoint
according to
0 = Absolute
priority
D.h.w.
1 = Shifting
priority
D.h.w.
2 = Shifting
priority
Maximum
selection
3 = None
(parallel)
D.h.w.
124 D.h.w. priority, flow
temperature set-
point
0
(0…4)
.........................
4 = None
(parallel)
Maximum
selection
Block “D.h.w. storage tank”
125 D.h.w. heating 0
(0…3)
.........................
0 = parallel with space heating
1 = alternating with space heat-
ing / electric; changeover ac-
cording to own controller
2 = alternating with space heat-
ing / electric; changeover ac-
cording to all controllers in
the interconnected system
that have the same segment
number
3 = alternating with space heat-
ing / electric; changeover ac-
cording to all controllers in the
interconnected system