The reset coil is available for dierent voltage supplies.
Technical specications AC DC Fuse determined from
characteristic curves
1)
Rated control supply
voltage U
s
24 V ✓ ✓ DIAZED fuse (operation‐
al class gL/gG) 10A TDz
(slow)
110 V ✓ ✓ DIAZED fuse (operation‐
al class gL/gG) 2A TDz
(slow)
220 V ✓ ✓
Operating limits (acc. to IEC 60947-2) 90 to 110% U
s
Switch-on power 90VA 90 W
1)
Miniature C-characteristic circuit breakers in accordance with VDE0641 with the same current rating
may be used as an alternative to fuses.
Mechanical operating cycles counter (MOC)
Unlike the communication link accessories, the mechanical operating cycles counter MOC does
not have a remote signaling option. It displays the number of mechanical switching operations
performed by the circuit breaker directly on the front of the circuit breaker.
Note
Because the number of operating cycles performed inuences the maintenance intervals, the
mechanical operating cycles counter MOC can provide the necessary basis for dening them.
You will nd information on maintenance in Chapter Service and maintenance (Page199)
The MOC can only be installed in conjunction with a spring charging motor.
Accessories
3.2Electromechanical accessories
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 99