What to do if my Siemens Circuit breaker cannot be closed?
- AAmy ColemanNov 3, 2025
If your Siemens Circuit breaker cannot be closed, it may not be ready for closure. Here are several potential causes and solutions: * The stored-energy spring may not be charged; charge the stored-energy spring. * The undervoltage release may not be energized; connect it to the power supply. * Mechanical reclosing lockout might be active; eliminate the trip cause by the electronic trip unit and press the reset button. * Electrical closing lockout might be active; disconnect the control voltage of the closing lockout. * If the O / OPEN button is locked with padlocks, remove them. If locked with a safety lock, release the O / OPEN button. * The emergency OPEN button may be locked; unlock it by turning it counterclockwise. * The lock to prevent closing when the control cabinet ...