Description   
2.5 Electronic trip unit ETU600 
  3WA1 air circuit breaker 
120  Equipment Manual, 02/2023, 92310000002-06 
2.5.5.6  Parameter DAS+ maintenance mode 
The settings for the maintenance mode DAS+ are independent of protection parameter 
sets A and B. 
 
i DAS+
n
g DAS+
g min
available, 
LSIG GFx 
g DAS+
available 
1)
  Depending on size 
 I
g min
: Sizes 1 and 2 = 100 A; size 3 = 400 A 
2.5.5.7  Zone-selective interlocking ZSI parameters 
The settings for the zone selective interlocking ZSI function are independent of 
protection parameter sets A and B. They require the presence of the ZSI200 module. 
Zone-selective interlocking ZSI (requires the ZSI200 module) 
 
Received signal acts on short-time-delayed short-circuit 
protection ST 
Received signal acts on ground-fault protection GF 
Sends signal on pick-up of short-time-delayed short-circuit 
protection ST  
Sends signal on pick-up of ground-fault protection GF 
Delay tZSI for short-time-delayed short-circuit protection ST 
Delay tZSI for ground-fault protection GF 
Monitoring of the ZSI200 module in the startup phase