Description
2.4 ETU300 electronic trip unit
3WA1 air circuit breaker
82 Equipment Manual, 02/2023, 92310000002-06
2.4.3.2 Digital input and output
The electronic trip unit ETU300 has one digital input and one digital output.
The input responds to a 24 V signal with signal level HIGH and activates the
maintenance mode DAS+.
The floating output is a normally open contact (NO). It is activated when the
maintenance mode DAS+ is active.
Technical specifications and connection
The connection is made at the secondary disconnect terminal system of the 3WA air
circuit breaker.
Voltage value for reliable detection of a "1
signal":
Current consumption at signal voltage of >15 V
DC
Normally open contact
(NO)
Maximum switching current
Maximum continuous current
• The digital input is designed for a control supply voltage of 24 V DC.
No polarity is specified at the DI ETU.0 and DI ETU.1 input terminals.
• The digital outputs DO ETU.0 and DO ETU.1 are designed for 24 V DC and as a
normally open contact (NO).
If the power to be switched exceeds the breaking capacity of the output, a suitable
coupling relay must be used.