Accessories
4.11 Accessories for the ETU300 and ETU600 electronic trip units
3WA1 air circuit breaker
358 Equipment Manual, 02/2023, 92310000002-06
4.11.6 Ready4COM thanks to BSS200 Breaker Status Sensor for ETU600
4.11.6.1 Description
The 3WA circuit breaker obtains the "ready4COM" feature thanks to the BSS200 Breaker
Status Sensor.
The BSS200 Breaker Status Sensor forms part of every circuit breaker with the ETU600
electronic trip unit with the "ready4COM" application package and metering function
PMF-I to PMF-III.
The BSS200 Breaker Status Sensor collects information about status states of the circuit
breaker with the signaling switch and transmits it to the CubicleBUS². In addition, it
controls the communication-capable CC-COM closing coil and the ST-COM shunt trip in
a circuit breaker with the ready4COM feature.
(1)
Connection for CC-COM closing coil and ST-COM shunt trip
(2)
Trip alarm switch S45
(3)
S43 signaling switch for second auxiliary release (ST2, UVR, or UVR-t)
(4)
Module with the signaling switches for ready for closing S40, spring charge status S41, and
main contacts (open/closed) S44
(5)
CubicleBUS² connection
(6)
Position signaling switch connected position S46 and test position S47