Integration in power distribution equipment
7.4 Requirement according to IEC 61439
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
527
7.4.2 Simplified integration
7.4.2.1 Structural integration in power distribution equipment
A 3WA circuit breaker can be installed without any testing or structural changes if
a 3WL circuit breaker has already been tested in the power distribution equipment.
The technical requirements for this are defined in IEC 61439-1:
The installation dimensions (terminals, cross-sections and mounting points) remain
unchanged.
The thermal losses and derating values of the circuit breaker are the same or better.
The arcing spaces are the same size or smaller.
The required main conductor connection cross-sections remain the same.
The copper connections stay the same.
The short-circuit breaking capacity (short circuit values I
cw
) for the power distribution
equipment remain the same.
The insulation conditions (required clearances and creepage distances) remain the
same.
The EMC classification is the same or higher.
The mechanical functions and operation remain the same.
The power distribution equipment design is unchanged.
You can find detailed information in Chapter Checklist for replacing 3WL with 3WA
circuit breaker according to IEC 61439-2 (Page 535).
Note
If a 3WL
circuit breaker is integrated, no m
echanical changes are required for integration
of the 3WA
circuit breaker.
Checks and tests
A short-circuit test is only necessary when the following two conditions are fulfilled:
Unlike the existing 3WL circuit breakers with article numbers 3WL….-…3.-. and
3WL….-…4.-…., the power distribution equipment is to be adapted to the higher
short-circuit breaking capacity of the 3WA circuit breakers.
The higher values of the 3WL circuit breakers with article numbers 3WL….-…6.-….
and 3WL.-…7.-…. have not been tested yet.
If the power distribution equipment is not designed for the increased short-circuit values,
the operator must make structural changes to the switchboard design.
No further tests (e.g. temperature-rise tests and EMC tests) are required.